Pepperl+Fuchs KCD2-RR-Ex1
Temperature Repeater

Pepperl+Fuchs KCD2-RR-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Resistance and RTD input (Pt100, Pt500, Pt1000)
  • Resistance output
  • Accuracy 0.1 %
  • Line fault detection (LFD) for Pt100
  • Housing width 12.5 mm
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-RR-Ex1
486.75
-
+
Total price: 486.75
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
KCD2-RR-EX1 286931

Available voltage0 ... 4.2 V

Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
- insertion bridge EBP 2- 5
EU-Type Examination CertificateBASEEFA 10 ATEX 0061
IECEx approvalIECEx BAS 10.0024
IECEx BAS 10.0025X
Connectionterminals 1, 2, 3, 4
Signal typeAnalog input
CertificateBASEEFA 10 ATEX 0062X
Line fault detectionyes , at Pt100
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Lead resistance10 % of resistance value
Rise timesignal response time 2 ms (10 ... 90 %)
response to application of Im: Rm > 50 andOmega; and Im < 5mA: < 5ms
response to application of Im: Rm > 30 andOmega; and Im < 5mA: < 10ms
response to application of Im: Rm > 18 andOmega; and Im < 5mA: < 20ms
Massapprox. 100 g
Line fault detection8 nA
Safety Integrity Level (SIL)SIL 2
ConnectionPower Rail or terminals 9+, 10-
Display elementsLED
Connectionscrew terminals
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Power consumption0.35 W (24 V and 1 mA sense current)
Electromagnetic compatibilityNE 21:2011
Fault signal< 10 andOmega; or > 400 andOmega;, depending on lead disconnected (measuring current 1 mA)
> 400 andOmega;, terminal 3 lead disconnected in 2-/4-wire (measuring current 0.3 mA)
Available voltage9 V
Current0 ... 10 mA
Connection sidecontrol side
Control elementsDIP-switch
Rated voltage19 ... 30 V DC
Configurationvia DIP switches
Connectionterminals 5-, 7-, 6+, 8+
Deviation4-wire
Im 1 mA: В±0.1 % of Rm or В± 0.1 andOmega; (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: В± 1 % of Rm or 1 andOmega; (the larger value is applicable).
3-wire
Im 1 mA: (В±0.1 % - 0.1 andOmega; Offset) or В± 0.2 andOmega; (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: (В±1 % - 0.1 andOmega; Offset) or В± 1.1 andOmega; (the larger value is applicable)
Labelingspace for labeling at the front
Transmission range0 ... 10 mA
Ripplewithin the supply tolerance
Connection sidefield side
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Rated current< 20 mA
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Accuracy0.1 %
Degree of protectionIP20
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Protection against electrical shockUL 61010-1
Degree of protectionIEC 60529:2001

Comments

No comments yet

Write a comment