Pepperl+Fuchs KCD2-RR-Ex1
Temperature Repeater
We ship to United States of America!
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Resistance and RTD input (Pt100, Pt500, Pt1000)
- Resistance output
- Accuracy 0.1 %
- Line fault detection (LFD) for Pt100
- Housing width 12.5 mm
- Up to SIL 2 acc. to IEC 61508
Item Number:
KCD2-RR-Ex1
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
KCD2-RR-EX1 286931 |
Available voltage0 ... 4.2 V
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) - insertion bridge EBP 2- 5 |
EU-Type Examination Certificate | BASEEFA 10 ATEX 0061 |
IECEx approval | IECEx BAS 10.0024 IECEx BAS 10.0025X |
Connection | terminals 1, 2, 3, 4 |
Signal type | Analog input |
Certificate | BASEEFA 10 ATEX 0062X |
Line fault detection | yes , at Pt100 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Lead resistance | 10 % of resistance value |
Rise time | signal response time 2 ms (10 ... 90 %) response to application of Im: Rm > 50 andOmega; and Im < 5mA: < 5ms response to application of Im: Rm > 30 andOmega; and Im < 5mA: < 10ms response to application of Im: Rm > 18 andOmega; and Im < 5mA: < 20ms |
Mass | approx. 100 g |
Line fault detection | 8 nA |
Safety Integrity Level (SIL) | SIL 2 |
Connection | Power Rail or terminals 9+, 10- |
Display elements | LED |
Connection | screw terminals |
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Power consumption | 0.35 W (24 V and 1 mA sense current) |
Electromagnetic compatibility | NE 21:2011 |
Fault signal | < 10 andOmega; or > 400 andOmega;, depending on lead disconnected (measuring current 1 mA) > 400 andOmega;, terminal 3 lead disconnected in 2-/4-wire (measuring current 0.3 mA) |
Available voltage | 9 V |
Current | 0 ... 10 mA |
Connection side | control side |
Control elements | DIP-switch |
Rated voltage | 19 ... 30 V DC |
Configuration | via DIP switches |
Connection | terminals 5-, 7-, 6+, 8+ |
Deviation | 4-wire Im 1 mA: ?±0.1 % of Rm or ?± 0.1 andOmega; (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ?± 1 % of Rm or 1 andOmega; (the larger value is applicable). 3-wire Im 1 mA: (?±0.1 % - 0.1 andOmega; Offset) or ?± 0.2 andOmega; (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: (?±1 % - 0.1 andOmega; Offset) or ?± 1.1 andOmega; (the larger value is applicable) |
Labeling | space for labeling at the front |
Transmission range | 0 ... 10 mA |
Ripple | within the supply tolerance |
Connection side | field side |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 |
Rated current | < 20 mA |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Accuracy | 0.1 % |
Degree of protection | IP20 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Protection against electrical shock | UL 61010-1 |
Degree of protection | IEC 60529:2001 |
Buy Pepperl+Fuchs KCD2-RR-Ex1 with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. provides complete industrial automation solutions. With a wide selection of products and efficient delivery options, we meet your needs effectively. Our focus on quality and customer satisfaction distinguishes us. Experience our exceptional service and support for your automation needs.
People also buy
Comments
No comments yet