Pepperl+Fuchs KCD2-RR-Ex1
Temperature Repeater

Pepperl+Fuchs KCD2-RR-Ex1
We ship to United States of America!
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Resistance and RTD input (Pt100, Pt500, Pt1000)
  • Resistance output
  • Accuracy 0.1 %
  • Line fault detection (LFD) for Pt100
  • Housing width 12.5 mm
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-RR-Ex1
486.75
-
+
Total price: 486.75
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
KCD2-RR-EX1 286931

Available voltage0 ... 4.2 V

Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
- insertion bridge EBP 2- 5
EU-Type Examination CertificateBASEEFA 10 ATEX 0061
IECEx approvalIECEx BAS 10.0024
IECEx BAS 10.0025X
Connectionterminals 1, 2, 3, 4
Signal typeAnalog input
CertificateBASEEFA 10 ATEX 0062X
Line fault detectionyes , at Pt100
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Lead resistance10 % of resistance value
Rise timesignal response time 2 ms (10 ... 90 %)
response to application of Im: Rm > 50 andOmega; and Im < 5mA: < 5ms
response to application of Im: Rm > 30 andOmega; and Im < 5mA: < 10ms
response to application of Im: Rm > 18 andOmega; and Im < 5mA: < 20ms
Massapprox. 100 g
Line fault detection8 nA
Safety Integrity Level (SIL)SIL 2
ConnectionPower Rail or terminals 9+, 10-
Display elementsLED
Connectionscrew terminals
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Power consumption0.35 W (24 V and 1 mA sense current)
Electromagnetic compatibilityNE 21:2011
Fault signal< 10 andOmega; or > 400 andOmega;, depending on lead disconnected (measuring current 1 mA)
> 400 andOmega;, terminal 3 lead disconnected in 2-/4-wire (measuring current 0.3 mA)
Available voltage9 V
Current0 ... 10 mA
Connection sidecontrol side
Control elementsDIP-switch
Rated voltage19 ... 30 V DC
Configurationvia DIP switches
Connectionterminals 5-, 7-, 6+, 8+
Deviation4-wire
Im 1 mA: В±0.1 % of Rm or В± 0.1 andOmega; (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: В± 1 % of Rm or 1 andOmega; (the larger value is applicable).
3-wire
Im 1 mA: (В±0.1 % - 0.1 andOmega; Offset) or В± 0.2 andOmega; (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: (В±1 % - 0.1 andOmega; Offset) or В± 1.1 andOmega; (the larger value is applicable)
Labelingspace for labeling at the front
Transmission range0 ... 10 mA
Ripplewithin the supply tolerance
Connection sidefield side
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Rated current< 20 mA
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Accuracy0.1 %
Degree of protectionIP20
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Protection against electrical shockUL 61010-1
Degree of protectionIEC 60529:2001

Buy Pepperl+Fuchs KCD2-RR-Ex1 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. provides complete industrial automation solutions. With a wide selection of products and efficient delivery options, we meet your needs effectively. Our focus on quality and customer satisfaction distinguishes us. Experience our exceptional service and support for your automation needs.

Comments

No comments yet

Write a comment