Pepperl+Fuchs KCD2-RR-Ex1
Temperature Repeater
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Resistance and RTD input (Pt100, Pt500, Pt1000)
- Resistance output
- Accuracy 0.1 %
- Line fault detection (LFD) for Pt100
- Housing width 12.5 mm
- Up to SIL 2 acc. to IEC 61508
Item Number:
KCD2-RR-Ex1
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
KCD2-RR-EX1 286931 |
Available voltage0 ... 4.2 V
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) - insertion bridge EBP 2- 5 |
EU-Type Examination Certificate | BASEEFA 10 ATEX 0061 |
IECEx approval | IECEx BAS 10.0024 IECEx BAS 10.0025X |
Connection | terminals 1, 2, 3, 4 |
Signal type | Analog input |
Certificate | BASEEFA 10 ATEX 0062X |
Line fault detection | yes , at Pt100 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Lead resistance | 10 % of resistance value |
Rise time | signal response time 2 ms (10 ... 90 %) response to application of Im: Rm > 50 andOmega; and Im < 5mA: < 5ms response to application of Im: Rm > 30 andOmega; and Im < 5mA: < 10ms response to application of Im: Rm > 18 andOmega; and Im < 5mA: < 20ms |
Mass | approx. 100 g |
Line fault detection | 8 nA |
Safety Integrity Level (SIL) | SIL 2 |
Connection | Power Rail or terminals 9+, 10- |
Display elements | LED |
Connection | screw terminals |
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Power consumption | 0.35 W (24 V and 1 mA sense current) |
Electromagnetic compatibility | NE 21:2011 |
Fault signal | < 10 andOmega; or > 400 andOmega;, depending on lead disconnected (measuring current 1 mA) > 400 andOmega;, terminal 3 lead disconnected in 2-/4-wire (measuring current 0.3 mA) |
Available voltage | 9 V |
Current | 0 ... 10 mA |
Connection side | control side |
Control elements | DIP-switch |
Rated voltage | 19 ... 30 V DC |
Configuration | via DIP switches |
Connection | terminals 5-, 7-, 6+, 8+ |
Deviation | 4-wire Im 1 mA: В±0.1 % of Rm or В± 0.1 andOmega; (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: В± 1 % of Rm or 1 andOmega; (the larger value is applicable). 3-wire Im 1 mA: (В±0.1 % - 0.1 andOmega; Offset) or В± 0.2 andOmega; (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: (В±1 % - 0.1 andOmega; Offset) or В± 1.1 andOmega; (the larger value is applicable) |
Labeling | space for labeling at the front |
Transmission range | 0 ... 10 mA |
Ripple | within the supply tolerance |
Connection side | field side |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 |
Rated current | < 20 mA |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Accuracy | 0.1 % |
Degree of protection | IP20 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Protection against electrical shock | UL 61010-1 |
Degree of protection | IEC 60529:2001 |
People also buy