Pepperl+Fuchs KCD2-RR-Ex1-Y1
Resistance repeater

Pepperl+Fuchs KCD2-RR-Ex1-Y1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Resistance and RTD input (Pt100, Pt500, Pt1000)
  • Resistance output
  • Accuracy 0.1 %
  • Housing width 12.5 mm
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-RR-Ex1-Y1
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview
  • Comments

ConnectionPower Rail or terminals 9+, 10-

Accuracy0.1 %
Rated current< 20 mA
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Labelingspace for labeling at the front
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Safety Integrity Level (SIL)SIL 2
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Electromagnetic compatibilityNE 21:2011
Available voltage0 ... 7 V
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
- insertion bridge EBP 2- 5
CertificateBASEEFA 10 ATEX 0062X
Massapprox. 100 g
Degree of protectionIP20
Connection sidefield side
Control elementsDIP-switch
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Lead resistance10 % of resistance value
Display elementsLED
Connection sidecontrol side
Configurationvia DIP switches
Connectionterminals 1, 2, 3, 4
Power consumption0.35 W (24 V and 1 mA sense current)
EU-Type Examination CertificateBASEEFA 10 ATEX 0061
Connectionterminals 5-, 7-, 6+, 8+
Ripplewithin the supply tolerance
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1
Available voltage9 V
Connectionscrew terminals
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Transmission range0 ... 10 mA
Current0 ... 10 mA
Rise timesignal response time 2 ms (10 ... 90 %)
response to application of Im: Rm > 50 andOmega; and Im < 5mA: < 5ms
response to application of Im: Rm > 30 andOmega; and Im < 5mA: < 10ms
response to application of Im: Rm > 18 andOmega; and Im < 5mA: < 20ms
Signal typeAnalog input
IECEx approvalIECEx BAS 10.0024
IECEx BAS 10.0025X
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
DeviationIm 1 mA: В±0.1 % of Rm or В± 0.1 andOmega; (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: В± 1 % of Rm or 1 andOmega; (the larger value is applicable).
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Rated voltage19 ... 30 V DC

Comments

No comments yet