Pepperl+Fuchs KCD2-RR2-Ex1.SP
Resistance Repeater

Pepperl+Fuchs KCD2-RR2-Ex1.SP
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Resistance and RTD input (Pt100, Pt500, Pt1000)
  • Resistance output
  • Accuracy 0.1 %
  • Line fault detection (LFD) for Pt100
  • Housing width 12.5 mm
  • Connection via spring terminals with push-in connection technology
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-RR2-Ex1.SP
414.34
-
+
Total price: 414.34
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Ambient temperature-40 ... 70 В°C (-40 ... 158 В°F)
EU-type examination certificateBASEEFA 10 ATEX 0061X
Rise time/fall time≤ 2 ms (10 ... 90%)
UL approvalE106378
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Connectionterminals 1, 2, 3, 4
Lead resistance≤ 10 % of resistance value
ConnectionPower Rail or terminals 9+, 10-
Safety Integrity Level (SIL)SIL 2
Connection sidecontrol side
Line fault detection< 30 nA
Electromagnetic compatibilityNE 21:2017
EN IEC 61326-3-2:2018
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
- insertion bridge EBP 2- 5
Reverse polarity protectionfor I < 10 mA or U < 20 V
Available voltage0 ... 4.2 V
Connection sidefield side
Power consumption0.35 W (24 V and 1 mA sense current), 0.85 W (30 V and 10 mA sense current)
Available voltage7 V
Transmission range0 ... 10 mA
Configurationvia DIP switches
CertificateBASEEFA 10 ATEX 0062X
DeviationIm ≥ 1 mA: В±0.1 % of Rm or В± 0.1 Ω (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: В± 1 % of Rm or 1 Ω (the larger value is applicable).
Degree of protectionIP20
Connectionspring terminals
Display elementsLED
Signal typeAnalog input
Fault signalfield voltage < 150 mV or > 4 V, depending on lead disconnected
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Rated voltage19 ... 30 V DC
Labelingspace for labeling at the front
Accuracy0.1 %
Control elementsDIP-switch
Connectionterminals 5-, 7-, 6+, 8+
Current0 ... 10 mA
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Degree of protectionIEC 60529:2001
Ripplewithin the supply tolerance
Line fault detectionyes , at Pt100
Settling time≤ 5 ms
Rated current< 28 mA
Protection against electrical shockUL 61010-1:2012
Massapprox. 100 g

Comments

No comments yet

Write a comment