Pepperl+Fuchs KCD2-SCD-Ex1
SMART Current Driver

Pepperl+Fuchs KCD2-SCD-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Current output up to 650 Omega- load
  • HART I/P and valve positioner
  • Lead breakage monitoring
  • Accuracy 0.1 %
  • Housing width 12.5 mm
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-SCD-Ex1
376.52
-
+
Total price: 376.52
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Connection side field side 

232717 art. KCD2-SCD-EX1
Voltage dropdepending on switch configuration
open loop voltage of the control system < 23 V: approx. 6 V at 20 mA
open loop voltage of the control system < 27 V: approx. 10 V at 20 mA
Load0 ... 650 andOmega;
Ripple10 %
Accuracy0.1 %
Connectionterminals 1+, 2-
Input signal4 ... 20 mA limited to approx. 30 mA
Input voltagedepending on switch configuration
open loop voltage of the control system < 23 V
open loop voltage of the control system < 27 V
Power consumption700 mW
Electromagnetic compatibilityNE 21
Connectionscrew terminals
Output/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Rated current30 mA
Display elementsLED
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Massapprox. 100 g
Connectionterminals 5-, 6+
Rated voltage19 ... 30 V DC
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
ConnectionPower Rail or terminals 9+, 10-
Safety Integrity Level (SIL)SIL 2
EU-Type Examination CertificateCESI 06 ATEX 021
Configurationvia DIP switches
IECEx approvalIECEx CES 06.0001
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Degree of protectionIP20
Degree of protectionIEC 60529
Power dissipation600 mW
Control elementsDIP-switch
Voltage13 V at 20 mA
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Deviationat 20 В°C (68 В°F), 0/4 ... 20 mA
В± 0.1 % incl. non-linearity and hysteresis
Input resistance> 100 kandOmega;, with field wiring open
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
CertificatePF 06 CERT 0973 X
Current4 ... 20 mA
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Signal typeAnalog output
Equipmentterminals 1+, 2-
Labelingspace for labeling at the front
Ripple20 mV rms
Connection sidecontrol side
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Rise time10 to 90 % 100 ms

Comments

No comments yet

Write a comment