Pepperl+Fuchs KCD2-SCD-Ex1.SP
SMART Current Driver

Pepperl+Fuchs KCD2-SCD-Ex1.SP
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Current output up to 650 Omega- load
  • HART I/P and valve positioner
  • Lead breakage monitoring
  • Accuracy 0.1 %
  • Housing width 12.5 mm
  • Connection via spring terminals
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-SCD-Ex1.SP
376.52
-
+
Total price: 376.52
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Output/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Degree of protectionIP20
Configurationvia DIP switches
Connectionspring terminals
Degree of protectionIP20 according to EN 60529
Rise time10 to 90 % 100 ms
Massapprox. 100 g
Display elementsLED
Load0 ... 650 andOmega;
Labelingspace for labeling at the front
Current4 ... 20 mA
Rated current 30 mA
Input resistance> 100 kandOmega;, with field wiring open
Deviationat 20 В°C (68 В°F), 0/4 ... 20 mA
В± 0.1 % incl. non-linearity and hysteresis
Power consumption 700 mW
Equipmentterminals 1+, 2-
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Signal typeAnalog output
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Input signal4 ... 20 mA limited to approx. 30 mA
Voltage dropdepending on switch configuration
open loop voltage of the control system < 23 V: approx. 6 V at 20 mA
open loop voltage of the control system < 27 V: approx. 10 V at 20 mA
Connectionterminals 5-, 6+
Power dissipation 600 mW
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
ConnectionPower Rail or terminals 9+, 10-
Input voltagedepending on switch configuration
open loop voltage of the control system < 23 V
open loop voltage of the control system < 27 V
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
IECEx approvalIECEx CES 06.0001
EU-Type Examination CertificateCESI 06 ATEX 021
Ripple20 mV rms
Connectionterminals 1+, 2-
Rated voltage19 ... 30 V DC
Accuracy0.1 %
Connection sidecontrol side
Connection sidefield side
Voltage 13 V at 20 mA
CertificatePF 06 CERT 0973 X
Ripple 10 %
Electromagnetic compatibilityNE 21
Control elementsDIP-switch
Safety Integrity Level (SIL)SIL 2
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff

Comments

No comments yet

Write a comment