Pepperl+Fuchs KCD2-SLD-Ex1.1245
Solenoid Driver
- 1-channel isolated barrier
- 24 V DC supply (bus or loop powered)
- Output 45 mA at 12 V DC
- Line fault transparency (LFT)
- Test pulse immunity
- Housing width 12.5 mm
- Up to SIL 3 acc. to IEC 61508
Item Number:
KCD2-SLD-Ex1.1245
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Output II/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
Output/other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC |
Current | typ. 45 mA |
Internal resistor | 240 andOmega; |
Test pulse length | max. 2 ms from DO card |
Signal type | Digital Output |
Current limit | 50 mA |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Display elements | LEDs |
Load | nominal 0.05 ... 18 kandOmega; |
Connection | terminals 1+, 2- |
Connection side | control side |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
UL approval | E106378 |
Line fault detection | signal at short-circuit RB < 25 andOmega;, lead breakage RB > 50 kandOmega; ; test current < 500 andmicro;A |
Protection against electrical shock | EN 61010-1:2010 |
Degree of protection | IP20 |
Mass | approx. 150 g |
Connection side | field side |
Power dissipation | 1.3 W at 24 V , 270 andOmega; load |
Labeling | space for labeling at the front |
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. |
Control elements | DIP-switch |
Degree of protection | IEC 60529:2013 |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: 36 mA (minimum load current DO card) |
Output II | fault signal |
Input current | 75 mA at 24 V , 270 andOmega; load |
Inrush current | < 200 mA , 10 ms loop powered |
Connection | terminals 5+, 6- |
Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered |
EU-Type Examination Certificate | EXA 17 ATEX 0002 X |
Open loop voltage | typ. 24.6 V |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Configuration | via DIP switches |
Connection | screw terminals |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Rated voltage | 19 ... 30 V DC loop powered |
Safety Integrity Level (SIL) | SIL 3 |
Voltage | typ. 12 V |