Pepperl+Fuchs KCD2-SOT-Ex2
Switch Amplifier

Pepperl+Fuchs KCD2-SOT-Ex2
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • 2 passive transistor outputs
  • Reversible mode of operation
  • Line fault detection (LFD)
  • Housing width 12.5 mm
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-SOT-Ex2
319.00
-
+
Total price: 319.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Signal level1-signal: (external voltage) - 3 V max. for 50 mA
0-signal: blocked output (off-state current ≤ 10 µA)
Degree of protectionIP20
Degree of protectionIEC 60529:2001
IECEx approvalIECEx BAS 13.0046
IECEx CML 19.0147X
Safety Integrity Level (SIL)SIL 2
Protection against electrical shockIEC 61010-1:2010
Response time≤ 200 µs
InputEN 60947-5-6:2000
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Massapprox. 100 g
Control elementsDIP-switch
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Configurationvia DIP switches
Connection sidecontrol side
Pulse/Pause ratiomin. 100 µs / min. 100 µs
Signal typeDigital Input
Connectionterminals 1+, 2-; 3+, 4-
ConnectionPower Rail or terminals 9+, 10-
Connection sidefield side
Collective error messagePower Rail
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Electromagnetic compatibilityNE 21:2011
Labelingspace for labeling at the front
Rated current50 mA
Dimensions12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
EU-type examination certificateBASEEFA 13 ATEX 0080
Display elementsLEDs
Ripple≤ 10 %
Rated current30 ... 20 mA
Output/power supplybasic insulation according to EN 50178, rated insulation voltage 50 Veff
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Connectionterminals 5, 6; 7, 8
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Output/Outputbasic insulation according to EN 50178, rated insulation voltage 50 Veff
Rated voltage30 V DC
CertificateCML 19 ATEX 4410 X
Power dissipation≤ 800 mW including maximum power dissipation in the output
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Connectionscrew terminals
Rated voltage19 ... 30 V DC
Output IIsignal ; Transistor
Output Isignal ; Transistor
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Switching frequency≤ 5 kHz