Pepperl+Fuchs KCD2-SR-1.LB.SP
Switch Amplifier
- 1-channel signal conditioner
- 24 V DC supply (Power Rail)
- Dry contact or NAMUR inputs
- Usable as signal splitter (1 input and 2 outputs)
- Relay contact output
- Fault relay contact output
- Line fault detection (LFD)
- Housing width 12.5 mm
- Connection via spring terminals with push-in connection technology
- Up to SIL 2 acc. to IEC 61508
Item Number:
KCD2-SR-1.LB.SP
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Control elements | DIP-switch |
Electromagnetic compatibility | NE 21:2006 |
Safety note | If load voltage > 50 V, de-energize before removing the terminals. |
Connection side | control side |
Connection | spring terminals |
Ripple | ≤ 10 % |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load |
Output I | signal ; relay |
Minimum switch current | 2 mA / 24 V DC |
Configuration | via DIP switches |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
Output/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Rated current | ≤ 30 mA |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Power dissipation | ≤ 500 mW |
Degree of protection | IEC 60529 |
Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Labeling | space for labeling at the front |
Display elements | LEDs |
Connection | output I: terminals 5, 6 ; output II: terminals 7, 8 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Output II | signal or error message ; relay |
Power consumption | ≤ 500 mW |
Output/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Mass | approx. 100 g |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Connection | terminals 1+, 2- |
Connection | Power Rail or terminals 9+, 10- |
Degree of protection | IP20 |
Mechanical life | 107 switching cycles |
Signal type | Digital Input |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Connection side | field side |
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Safety Integrity Level (SIL) | SIL 2 |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Switching frequency | ≤ 10 Hz |
Rated voltage | 19 ... 30 V DC |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |