Pepperl+Fuchs KCD2-SR-2
Switch Amplifier
We ship to United States of America!
- 2-channel signal conditioner
- 24 V DC supply (Power Rail)
- Dry contact or NAMUR inputs
- Relay contact output
- Line fault detection (LFD)
- Housing width 12.5 mm
- Up to SIL 2 acc. to IEC 61508
Item Number:
KCD2-SR-2
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
- Overview +
- Comments +
Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Output II | signal ; relay |
Ripple | 10 % |
Degree of protection | IP20 |
Mechanical life | 107 switching cycles |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
Connection | screw terminals |
Power consumption | 600 mW |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Rated voltage | 19 ... 30 V DC |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Output I | signal ; relay |
Mass | approx. 100 g |
Line fault detection | breakage I 0.1 mA , short-circuit I 6.5 mA |
Output/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Input/input | Basic insulation according to EN 50178, rated insulation voltage 300 Veff |
Switching frequency | 10 Hz |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Control elements | DIP-switch |
Electromagnetic compatibility | NE 21:2006 |
Contact loading | 253 V AC/2 A/cos andphi; > 0.7; 126.5 V AC/4 A/cos andphi; > 0.7; 30 V DC/2 A resistive load |
Labeling | space for labeling at the front |
Display elements | LEDs |
Degree of protection | IEC 60529 |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Connection side | control side |
Connection | Power Rail or terminals 9+, 10- |
Signal type | Digital Input |
Connection | terminals 1+, 2-; 3+, 4- |
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Minimum switch current | 2 mA / 24 V DC |
Safety Integrity Level (SIL) | SIL 2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Connection side | field side |
Connection | terminals 5, 6; 7, 8 |
Configuration | via DIP switches |
Rated current | 30 mA |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Output/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Power dissipation | 600 mW |
Energized/De-energized delay | 20 ms / 20 ms |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Buy Pepperl+Fuchs KCD2-SR-2 with the best possible price and delivery terms on eltra-trade.com
Discover a wide selection of industrial electrical products at eltra-trade.com. We specialize in sourcing and delivering the parts you need promptly. Our commitment to quality and competitive pricing sets us apart. Partner with us for reliable and efficient electrical supply solutions.
People also buy