Pepperl+Fuchs KCD2-SR-Ex1.LB
Switch Amplifier
We ship to United States of America!
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Dry contact or NAMUR inputs
- Usable as signal splitter (1 input and 2 outputs)
- Relay contact output
- Fault relay contact output
- Line fault detection (LFD)
- Housing width 12.5 mm
- Up to SIL 2 acc. to IEC 61508
Item Number:
KCD2-SR-Ex1.LB
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
- Overview +
- Comments +
Output/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Display elements | LEDs |
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Connection | output I: terminals 5, 6 ; output II: terminals 7, 8 |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Ripple | 10 % |
Mechanical life | 107 switching cycles |
Rated voltage | 19 ... 30 V DC |
Line fault detection | breakage I 0.1 mA , short-circuit I 6.5 mA |
Minimum switch current | 2 mA / 24 V DC |
Connection | screw terminals |
Power consumption | 500 mW |
Control elements | DIP-switch |
Energized/De-energized delay | 20 ms / 20 ms |
Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Configuration | via DIP switches |
Certificate | PF 06 CERT 0972 X |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Output I | signal ; relay |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Connection | Power Rail or terminals 9+, 10- |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Safety Integrity Level (SIL) | SIL 2 |
Connection side | field side |
Power dissipation | 500 mW |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
Degree of protection | IEC 60529:2001 |
Switching frequency | 10 Hz |
Connection side | control side |
IECEx approval | IECEx BAS 06.0025 |
EU-Type Examination Certificate | BASEEFA 06 ATEX 0092 |
Rated current | 30 mA |
Electromagnetic compatibility | NE 21 |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Signal type | Digital Input |
Output/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Degree of protection | IP20 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Connection | terminals 1+, 2- |
Labeling | space for labeling at the front |
Contact loading | 253 V AC/2 A/cos andphi; > 0.7; 126.5 V AC/4 A/cos andphi; > 0.7; 30 V DC/2 A resistive load |
Output II | signal or error message ; relay |
Mass | approx. 100 g |
Buy Pepperl+Fuchs KCD2-SR-Ex1.LB with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. delivers top-quality industrial control products. Our extensive inventory ensures you find the parts you need, with worldwide delivery options. We offer competitive prices and personalized service. Get in touch today to see how we can support your business effectively and efficiently.