Pepperl+Fuchs KCD2-SR-Ex1.LB.SP
Switch Amplifier
We ship to United States of America!
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Dry contact or NAMUR inputs
- Usable as signal splitter (1 input and 2 outputs)
- Relay contact output
- Fault relay contact output
- Line fault detection (LFD)
- Housing width 12.5 mm
- Connection via spring terminals with push-in connection technology
- Up to SIL 2 acc. to IEC 61508
Item Number:
KCD2-SR-Ex1.LB.SP
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
- Overview +
- Comments +
Safety note | If load voltage > 50 V, de-energize before removing the terminals. |
Output II | signal or error message ; relay |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Electromagnetic compatibility | NE 21 |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Labeling | space for labeling at the front |
Configuration | via DIP switches |
Connection side | control side |
Degree of protection | IP20 |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load |
Certificate | PF 06 CERT 0972 X |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Ripple | ≤ 10 % |
Output/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Signal type | Digital Input |
Mass | approx. 100 g |
Safety Integrity Level (SIL) | SIL 2 |
Rated voltage | 19 ... 30 V DC |
Display elements | LEDs |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Output I | signal ; relay |
Mechanical life | 107 switching cycles |
Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Connection | spring terminals |
EU-type examination certificate | BASEEFA 06 ATEX 0092 |
Output/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
Rated current | ≤ 30 mA |
Connection | output I: terminals 5, 6 ; output II: terminals 7, 8 |
Power dissipation | ≤ 500 mW |
Connection | Power Rail or terminals 9+, 10- |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Degree of protection | IEC 60529:2001 |
IECEx approval | IECEx BAS 06.0025 |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
Switching frequency | ≤ 10 Hz |
Control elements | DIP-switch |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Power consumption | ≤ 500 mW |
Input/power supply | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff |
Connection side | field side |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Connection | terminals 1+, 2- |
Minimum switch current | 2 mA / 24 V DC |
Buy Pepperl+Fuchs KCD2-SR-Ex1.LB.SP with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com offers electrical parts online. Our product range includes industrial sensors, motor control components, pneumatic automation, and many other automation equipment. We ship to any country as quickly as possible. By providing you with minimum prices, you can save money. You will be pleased to work with us. Our clients include a large number of well-known global manufacturing companies.