Pepperl+Fuchs KCD2-SR-Ex2.SP
Switch Amplifier

Pepperl+Fuchs KCD2-SR-Ex2.SP
We ship to United States of America!
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Relay contact output
  • Line fault detection (LFD)
  • Housing width 12.5 mm
  • Connection via spring terminals with push-in connection technology
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-SR-Ex2.SP
195.72
-
+
Total price: 195.72
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
  • Overview +
  • Comments +
Connectionspring terminals
Configurationvia DIP switches
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Labelingspace for labeling at the front
Display elementsLEDs
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Power consumption≤ 600 mW
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Connectionterminals 5, 6; 7, 8
Control elementsDIP-switch
Massapprox. 100 g
Connection sidefield side
Signal typeDigital Input
Rated current≤ 30 mA
Minimum switch current2 mA / 24 V DC
Safety Integrity Level (SIL)SIL 2
IECEx approvalIECEx BAS 06.0025
Output/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Safety noteIf load voltage > 50 V, de-energize before removing the terminals.
Dimensions12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Ambient temperature-20 ... 60 ?°C (-4 ... 140 ?°F)
Rated voltage19 ... 30 V DC
Mechanical life107 switching cycles
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Ripple≤ 10 %
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
EU-type examination certificateBASEEFA 06 ATEX 0092
Degree of protectionIP20
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
CertificatePF 06 CERT 0972 X
ConnectionPower Rail or terminals 9+, 10-
Output/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Degree of protectionIEC 60529:2001
Output IIsignal ; relay
Electromagnetic compatibilityNE 21
Connectionterminals 1+, 2-; 3+, 4-
Output Isignal ; relay
Power dissipation≤ 600 mW
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Switching frequency≤ 10 Hz
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Input/inputBasic insulation according to EN 50178, rated insulation voltage 300 Veff
Connection sidecontrol side