Pepperl+Fuchs KCD2-ST-2
Switch Amplifier

Pepperl+Fuchs KCD2-ST-2
We ship to United States of America!
  • 2-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • 2 active transistor outputs
  • Reversible mode of operation
  • Line fault detection (LFD)
  • Housing width 12.5 mm
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-ST-2
205.10
-
+
Total price: 205.10
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Signal typeDigital Input
Rated current50 mA
Collective error messagePower Rail
Output/Outputnot available , common pole terminal 9+
Rated current30 ... 20 mA + Iout
Connectionterminals 5, 6
Degree of protectionIEC 60529:2001
Safety Integrity Level (SIL)SIL 2
ConnectionPower Rail or terminals 9+, 10-
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Response time≤ 200 µs
Pulse/Pause ratiomin. 100 µs / min. 100 µs
Output Isignal ; Transistor
Switching frequency≤ 5 kHz
Output IIsignal ; Transistor
Labelingspace for labeling at the front
Degree of protectionIP20
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Connectionterminals 1+, 2-; 3+, 4-
Ripple≤ 10 %
Connection sidecontrol side
Display elementsLEDs
Massapprox. 100 g
Signal level1-signal: (supply voltage) - 3 V max. for 50 mA
0-signal: blocked output (off-state current ≤ 10 µA)
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Rated voltage30 V DC
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Power dissipation≤ 800 mW including maximum power dissipation in the output
Configurationvia DIP switches
Protection against electrical shockIEC 61010-1:2010
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
InputEN 60947-5-6:2000
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Output/power supplynot available , common pole terminal 9+
Dimensions12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Rated voltage19 ... 30 V DC
Connectionscrew terminals
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Control elementsDIP-switch
Connection sidefield side
Electromagnetic compatibilityNE 21:2011
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff

Buy Pepperl+Fuchs KCD2-ST-2 with the best possible price and delivery terms on eltra-trade.com

eltra-trade.com is your reliable source for industrial electrical parts. Our extensive product range includes various automation equipment, all available for fast delivery. We guarantee quality and competitive prices. Make us your preferred partner for all your electrical supply needs.

Comments

No comments yet