Pepperl+Fuchs KCD2-STC-Ex1.2O.ES
SMART Transmitter Power Supply

Pepperl+Fuchs KCD2-STC-Ex1.2O.ES
We ship to United States of America!
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input for 2-wire SMART transmitters and current sources
  • Signal splitter (1 input and 2 outputs)
  • Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V
  • Terminal blocks with test sockets
  • Up to SIL 3 acc. to IEC 61508
Item Number: KCD2-STC-Ex1.2O.ES
694.15
-
+
Total price: 694.15
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Configurationvia DIP switches
Protection against electrical shockUL 61010-1:2012
EU-Type Examination CertificateBASEEFA 13 ATEX 0077 X
Safety Integrity Level (SIL)SIL 3
Massapprox. 100 g
Power dissipationapprox. 1.4 W at 20 mA transfer current, 250 andOmega; in both outputs
Rated voltage18 ... 30 V DC
Ripplewithin the supply tolerance
Rise time/fall time2 ms
DeviationIout < 20 andmicro;A (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 В°C (68 В°F), 0/4 ... 20 mA, 0/1 ... 5 V
Output signal0/4 ... 20 mA or 0/1 ... 5 V
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Signal typeAnalog input
Output/Outputfunctional insulation, rated insulation voltage 50 V AC
Loadchannel 1: 0 ... 500 andOmega; (20 mA)/> 1 MandOmega; (5 V)
channel 2: 0 ... 500 andOmega; (20 mA)/> 1 MandOmega; (5 V)
Equipmentterminals 3+, 4-
Settling time6 ms
Connectionterminals 1+, 2- (sink); 3+, 4- (source)
Labelingspace for labeling at the front
Control elementsDIP-switch
Ripplemax. 50 andmicro;A rms
Dimensions12.5 x 114 x 122 mm (0.5 x 4.5 x 4.8 inch) , housing type A2
Display elementsLED
Connection sidefield side
Voltage dropterminals 3, 4: 6.1 V at 20 mA
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB)
Degree of protectionIEC 60529:2001
Equipmentterminals 1+, 2-
NoteBoth output loads must be connected to ensure complete and correct operation within the technical specification.
Connectionscrew terminals
Degree of protectionIP20
Connectionsource: terminals 5-, 6+; 7-, 8+
sink: terminals 5+, 6-, 7+, 8-
Input signal0/4 ... 20 mA
Available voltageterminals 1+, 2-: 16 V at 20 mA , 18.5 V at 4 mA
Short-circuit currentterminals 1+, 2-: 25 mA
Power consumption2 W
Connection sidecontrol side
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
IECEx approvalIECEx BAS 13.0043X
CertificateBASEEFA 13 ATEX 0078 X
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Input resistanceterminals 1+, 2-: max. 500 andOmega;
(250 andOmega; load)
ConnectionPower Rail or terminals 9+, 10-

Buy Pepperl+Fuchs KCD2-STC-Ex1.2O.ES with the best possible price and delivery terms on eltra-trade.com

Discover a wide variety of industrial electrical products at eltra-trade.com. We specialize in sourcing and delivering the parts you need promptly. Our commitment to quality and competitive pricing sets us apart. Partner with us for reliable and efficient electrical supply solutions.