Pepperl+Fuchs KCD2-STC-Ex1.SP
SMART Transmitter Power Supply

Pepperl+Fuchs KCD2-STC-Ex1.SP
We ship to United States of America!
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input for 2-wire SMART transmitters and current sources
  • Output for 4 mA ... 20 mA or 1 V ... 5 V
  • Sink or source mode
  • Housing width 12.5 mm
  • Connection via spring terminals
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-STC-Ex1.SP
Price on Request
-
+
Total price: 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +
Degree of protectionIEC 60529:2001
Input signal4 ... 20 mA limited to approx. 30 mA
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Control elementsDIP-switch
Connectionterminals 1+, 2-; 3+, 4-
Voltage dropterminals 3+, 4- : approx. 5 V
Safety Integrity Level (SIL)SIL 2
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Settling time 200 ms
Massapprox. 100 g
Deviationat 20 ?°C (68 ?°F)
?± 0.1 % incl. non-linearity and hysteresis (source mode 4 ... 20 mA)
?± 0.2 % incl. non-linearity and hysteresis (sink mode 4 ... 20 mA)
?± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
Rise time/fall time 20 ms
Load0 ... 300 andOmega; (source mode)
Degree of protectionIP20
Output/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Equipmentterminals 1+, 2-
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
ConnectionPower Rail or terminals 9+, 10-
Ripple 10 %
CertificatePF 06 CERT 0973 X
Equipmentterminals 3+, 4-
Output signal4 ... 20 mA or 1 ... 5 V (on 250 andOmega;, 0.1 % internal shunt)
4 ... 20 mA (sink mode), operating voltage 15.5 ... 26 V
Ripple20 mV rms
IECEx approvalIECEx CES 06.0001
Connectionterminals 5-, 6+
Labelingspace for labeling at the front
Power consumption 1.1 W
EU-Type Examination CertificateCESI 06 ATEX 021
Connection sidefield side
Signal typeAnalog input
Ambient temperature-20 ... 60 ?°C (-4 ... 140 ?°F)
Rated current 45 mA
Available voltageterminals 1+, 2-: 15 V at 20 mA
Display elementsLED
Electromagnetic compatibilityNE 21:2006
Open circuit voltage/short-circuit currentterminals 1+, 2-: 22 V / 30 mA
Rated voltage19 ... 30 V DC
Power dissipation 800 mW
Connection sidecontrol side
Configurationvia DIP switches
Connectionspring terminals
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff

Buy Pepperl+Fuchs KCD2-STC-Ex1.SP with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. provides complete industrial automation solutions. With a wide selection of products and efficient delivery options, we meet your needs effectively. Our focus on quality and customer satisfaction distinguishes us. Experience our exceptional service and support for your automation needs.