Pepperl+Fuchs KCD2-STC-Ex1.SP
SMART Transmitter Power Supply

Pepperl+Fuchs KCD2-STC-Ex1.SP
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input for 2-wire SMART transmitters and current sources
  • Output for 4 mA ... 20 mA or 1 V ... 5 V
  • Sink or source mode
  • Housing width 12.5 mm
  • Connection via spring terminals
  • Up to SIL 2 acc. to IEC 61508
Item Number: KCD2-STC-Ex1.SP
368.27
-
+
Total price: 368.27
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Degree of protectionIEC 60529:2001
Input signal4 ... 20 mA limited to approx. 30 mA
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Control elementsDIP-switch
Connectionterminals 1+, 2-; 3+, 4-
Voltage dropterminals 3+, 4- : approx. 5 V
Safety Integrity Level (SIL)SIL 2
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Settling time 200 ms
Massapprox. 100 g
Deviationat 20 В°C (68 В°F)
В± 0.1 % incl. non-linearity and hysteresis (source mode 4 ... 20 mA)
В± 0.2 % incl. non-linearity and hysteresis (sink mode 4 ... 20 mA)
В± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
Rise time/fall time 20 ms
Load0 ... 300 andOmega; (source mode)
Degree of protectionIP20
Output/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Equipmentterminals 1+, 2-
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
ConnectionPower Rail or terminals 9+, 10-
Ripple 10 %
CertificatePF 06 CERT 0973 X
Equipmentterminals 3+, 4-
Output signal4 ... 20 mA or 1 ... 5 V (on 250 andOmega;, 0.1 % internal shunt)
4 ... 20 mA (sink mode), operating voltage 15.5 ... 26 V
Ripple20 mV rms
IECEx approvalIECEx CES 06.0001
Connectionterminals 5-, 6+
Labelingspace for labeling at the front
Power consumption 1.1 W
EU-Type Examination CertificateCESI 06 ATEX 021
Connection sidefield side
Signal typeAnalog input
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Rated current 45 mA
Available voltageterminals 1+, 2-: 15 V at 20 mA
Display elementsLED
Electromagnetic compatibilityNE 21:2006
Open circuit voltage/short-circuit currentterminals 1+, 2-: 22 V / 30 mA
Rated voltage19 ... 30 V DC
Power dissipation 800 mW
Connection sidecontrol side
Configurationvia DIP switches
Connectionspring terminals
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff

Comments

No comments yet

Write a comment