Pepperl+Fuchs KCD2-UT2-Ex1
Universal Temperature Converter

Pepperl+Fuchs KCD2-UT2-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Thermocouple, RTD, potentiometer or voltage input
  • Current output 0/4 mA ... 20 mA
  • Sink or source mode
  • Configurable by PACTware
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number: KCD2-UT2-Ex1
562.15
-
+
Total price: 562.15
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

CertificateBASEEFA 13 ATEX 0103 X
Massapprox. 100 g
Signal typeAnalog input
OutputAnalog current output
Degree of protectionIP20
EU-Type Examination CertificateBASEEFA 13 ATEX 0102 X
Connectionterminals 9+, 10- or power feed module/Power Rail
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Programming interfaceprogramming socket
IECEx approvalIECEx BAS 13.0057X
Connection sidefield side
Electromagnetic compatibilityNE 21:2011
Configurationvia PACTware
Degree of protectionIEC 60529:2001
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s
Input resistance1 MandOmega; (-100 ... 100 mV)
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Connection sidecontrol side
Ripplewithin the supply tolerance
Connectionscrew terminals
Display elementsLEDs
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
Rated voltage19 ... 30 V DC
Labelingspace for labeling at the front
Connectionterminals 1, 2, 3, 4
Connectionterminal 5: source (-), terminal 6: source (+), terminal 7: sink(-), terminal 8: sink (+)
Voltageselectable within the range -100 ... 100 mV
Inputsterminals 1, 2, 3, 4
Output/supply, programming inputfunctional insulation, rated insulation voltage 50 V AC
There is no electrical isolation between the programming input and the supply.
The programming cable provides galvanic isolation so that ground loops are avoided.
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Protection against electrical shockUL 61010-1:2004
Potentiometer0 ... 20 kandOmega; (2-wire connection), 0.8 ... 20 kandOmega; (3-wire connection)
Safety Integrity Level (SIL)SIL 2
Power dissipation/power consumption0.98 W / 0.98 W

Comments

No comments yet

Write a comment