Rated voltage207 ... 253 V AC, 45 ... 65 Hz
Output I, IIsignal ; relay
Mechanical life107 switching cycles
Switching frequency 10 Hz
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Degree of protectionIEC 60529:2001
Degree of protectionIP20
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Connection sidecontrol side
Power dissipation1.2 W
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Safety Integrity Level (SIL)SIL 2
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Output/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Rated valuesacc. to EN 60947-5-6 (NAMUR)
InputEN 60947-5-6:2000
IECEx approvalIECEx PTB 11.0031
Massapprox. 150 g
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Connectionoutput I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Contact loading253 V AC/2 A/cos andphi; > 0.7; 126.5 V AC/4 A/cos andphi; > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Connection sidefield side
Connectionterminals 1+, 2+, 3-; 4+, 5+, 6-
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Line fault detectionbreakage I 0.1 mA , short-circuit I > 6 mA
Power consumptionmax. 1.3 W
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Connectionterminals 14, 15
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Electromagnetic compatibilityNE 21:2006
Signal typeDigital Input
Labelingspace for labeling at the front
Connectionscrew terminals
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
EU-Type Examination CertificatePTB 00 ATEX 2081
Display elementsLEDs

Buy Pepperl+Fuchs KFA6-SR2-Ex2.W with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. offers electrical supplies online. We offer 50+ automation equipment brands. For your convenience, we can arrange express delivery worldwide. Guaranteed quality with the minimum possible prices. You don't need to pay in advance if you are our regular customer. Ordering from us you will get convenience and high speed of purchase.