Pepperl+Fuchs KFD0-CS-Ex2.54 Repeater


Item Number: KFD0-CS-Ex2.54
- 2-channel isolated barrier
- 24 V DC supply (loop powered)
- SMART fire alarm input
- Current input 1 mA ... 20 mA
- Up to SIL 3 acc. to IEC 61508
- Overview
- Datasheet
- Alternative numbers
- Comments
Protection against electrical shock | UL 61010-1 |
EU-type examination certificate | BAS 00 ATEX 7087 |
Current | 0 ... 20 mA |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
Transmission range | current: 1 ... 20 mA voltage: 4 ... 20 V DC / 0 ... 6 Vss AC |
Connection | screw terminals |
Signal type | Analog input |
Labeling | space for labeling at the front |
Rated voltage | loop powered |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Connection | terminals 1+, 2-; 4+, 5- |
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Short-circuit current | ≤ 65 mA |
Degree of protection | IP20 |
Power dissipation | < 0.2 W for Uin = 24 V, Io = 20 mA |
Rise time/fall time | ≤ 50 µs (load current ≥ 1 mA) |
Certificate | TГњV 99 ATEX 1499 X |
Connection | terminals 11+, 12-; 9+, 10-, 8- |
Degree of protection | IEC 60529:2001 |
Voltage | 0 ... 24 V for 4 V ≤ Ue ≤ 24 V: ≥ Ue - (0.41 x input current in mA) - 0.5 |
Electromagnetic compatibility | NE 21:2006 |
Mass | approx. 100 g |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Safety Integrity Level (SIL) | SIL 3 |