Pepperl+Fuchs KFD0-RO-Ex2
Relay Module

Pepperl+Fuchs KFD0-RO-Ex2
We ship to United States of America!
  • 2-channel isolated barrier
  • 24 V DC supply (loop powered)
  • Logic input 15 V DC ... 30 V DC, non-polarized
  • Relay contact output
  • Up to SIL 3 acc. to IEC 61508
Item Number: KFD0-RO-Ex2
158.32
-
+
Total price: 158.32
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
  • Overview +
  • Comments +

The KFD0-RO-Ex2 is a relay output module ideal for switching applications in hazardous areas. It features two relay outputs with configurable options, ensuring flexibility in various control scenarios, such as remote switching of alarms or other field devices.

Datasheet:

Display elementsLEDs
Mechanical life5 x 106 switching cycles
Massapprox. 100 g
Connection sidecontrol side
Switching frequency< 10 Hz
Ambient temperature-20 ... 65 ?°C (-4 ... 149 ?°F)
CertificateT??V 00 ATEX 1621 X
Power dissipation0.8 W
Output/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
IECEx approvalIECEx BVS 10.0025
EU-Type Examination CertificateDMT 00 ATEX E 016
Labelingspace for labeling at the front
Safety noteAttention! Combination of output Ex i with output not Ex i is not permitted.
If load voltage > 50 V, de-energize before removing the terminals.
Connectionscrew terminals
Input current 21 mA per channel
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Connectionterminals 1, 2, 3; 4, 5, 6
Signal typeDigital Output
Degree of protectionIEC 60529:2001
Energized/De-energized delayapprox. 10 ms / approx. 5 ms
Contact loading230 V AC/2 A/cos andphi; > 0.7; 40 V DC/2 A resistive load
Degree of protectionIP20
Connection sidefield side
Rated voltageloop powered
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input voltage15 ... 30 V DC
Safety Integrity Level (SIL)SIL 3
Connectionterminals 7, 8, 9
Electromagnetic compatibilityNE 21:2006

Buy Pepperl+Fuchs KFD0-RO-Ex2 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. is an online electrical distributor. Here you can find any spare part you need. All your items can be combined and sent in one delivery. Prices and delivery conditions are our main focus. We provide free delivery for our regular customers. Our services will save you time and money which on the other side will help you grow your business!