Pepperl+Fuchs KFD0-TR-1
RTD Converter

Pepperl+Fuchs KFD0-TR-1
  • 1-channel signal conditioner
  • 24 V DC supply (loop powered)
  • 2- or 3-wire Pt100 RTD input
  • Output 4 mA ... 20 mA, temperature linearization selectable
  • DIP switch selectable ranges
  • Sensor breakage detection
Item Number: KFD0-TR-1
195.00
-
+
Total price: 195.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Degree of protectionIEC 60529
Input/Outputsafe isolation acc. to DIN VDE 0106, rated insulation voltage 253 Veff
Massapprox. 150 g
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Measurement rangespan without linearization 25 ... 800 В°C (77 ... 1472 В°F)/ with linearisation 25 ... 375 В°C (77 ... 707 В°F)
zero point without linearization -200 ... 400 В°C (-328 ... 752 В°F)/ with linearisation -30 ... 375 В°C (-22 ... 707 В°F)
span and zero point adjustable
Insulation coordinationEN 50178
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Rated voltage12 ... 35 V DC loop powered
Rise time250 ms
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Degree of protectionIP20
Fault signalsensor burnout: upscaling 22 mA , limited to 35 mA
Power dissipation0.4 W
Control elementsDIP-switch
rotary switch
Connectionscrew terminals
Configurationvia DIP switches
via rotary switch
Connectionterminals 1, 2-, 3+
suitable for Pt100, 2- and 3-wire connection
Measuring currentapprox. 1 mA
Connection sidecontrol side
Current output4 ... 20 mA , limited to 35 mA
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Galvanic isolationEN 50178
Signal typeAnalog input
Lead resistancemax. 100 andOmega; per line
Load(U -12 V) / 0.02 A
Connection sidefield side
Labelingspace for labeling at the front
Connectionterminals 9+, 8-

Comments

No comments yet