Pepperl+Fuchs KFD0-TR-Ex1
RTD Converter
- 1-channel isolated barrier
- 24 V DC supply (loop powered)
- 2- or 3-wire Pt100 RTD input
- Output 4 mA ... 20 mA, temperature linearization selectable
- DIP switch selectable ranges
- Sensor breakage detection
Item Number:
KFD0-TR-Ex1
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Rise time250 ms
Input/Output | available |
Lead resistance | max. 100 andOmega; per line |
Control elements | DIP-switch rotary switch |
Connection | screw terminals |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Mass | approx. 150 g |
Insulation coordination | EN 50178 |
Degree of protection | IEC 60529 |
Signal type | Analog input |
Connection side | control side |
Measurement range | span without linearization 25 ... 800 В°C (77 ... 1472 В°F)/with linearization 25 ... 375 В°C (77 ... 707 В°F), both adjustable zero point without linearization -200 ... 400 В°C (-328 ... 752 В°F)/with linearization -30 ... 375 В°C (-22 ... 707 В°F), both adjustable |
Galvanic isolation | EN 50178 |
Current output | 4 ... 20 mA , limited to 35 mA |
Configuration | via DIP switches via rotary switch |
Connection | terminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection |
Certificate | TГњV 01 ATEX 1777 X |
Connection | terminals 9+, 8- |
Power dissipation | 0.4 W |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Load | (U -12 V) / 0.02 A |
Measuring current | approx. 1 mA |
Fault signal | upscaling 22 mA (limited to 35 mA) |
Labeling | space for labeling at the front |
EU-Type Examination Certificate | ZELM 00 ATEX 0036 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Rated voltage | 12 ... 35 V DC loop powered |
Degree of protection | IP20 |
Connection side | field side |