Pepperl+Fuchs KFD2-BR-1.PA.1500 Basic Segment Coupler

Pepperl+Fuchs KFD2-BR-1.PA.1500
Item Number: KFD2-BR-1.PA.1500
  • Output: 24 ... 26 V/400 mA
  • Couples PROFIBUS PA devices transparently to PROFIBUS DP
  • High-power trunk for high device count and long cable lengths
  • Installation in Zone 2/Class I, Div. 2
  • Up to 1.5 MBit auto-adapting
  • PROFIBUS DP terminator selectable
  • Power Rail support
1100.40
Quantity
-
+
Total price: 1100.40
Contact our experts
  • Overview
  • Datasheet
  • Alternative numbers
  • PDF
  • Comments

IECEx approvalIECEx TUR 16.0006X

Shock resistanceEN 60068-2-27
Shock resistance15 g 11 ms
Vibration resistanceEN 60068-2-6
Degree of protectionIP20
LED DP/ERRred 2 Hz flashing: DP error red on: Hardware error red off: DP communication detected
Ripple10 %
Housing materialPolycarbonate
PROFIBUS PA/Supplybasic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC
Relative humidity< 95 % non-condensing
Vibration resistance1 g 10 ... 150 Hz
MountingDIN rail mounting
Rated voltage20 ... 30 V DC
Design / MountingCabinet installation
Ambient temperature-40 ... 60 В°C (-40 ... 140 В°F)
Rated current640 mA ... 365 mA
Power dissipationmax 2.5 W
SwitchPROFIBUS DP terminator
Mass180 g
PROFIBUS DP/Supplybasic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Fieldbus standardEN 50170/2
ConnectionPower Rail or terminals 11 (L+), 12 (L-)
LED PWRgreen: Power on
Statement of conformityTГњV 16 ATEX 7831 X
Core cross-sectionup to 2.5 mm2
Pollution degreemax. 2, according to IEC 60664
LED PAred 2 Hz flashing: No PA communication or overload Off: PA communication OK
Storage temperature-40 ... 85 В°C (-40 ... 185 В°F)
Climatic conditionsDIN IEC 721
PROFIBUS DP/PROFIBUS PAfunctional insulation acc. to IEC 62103, rated insulation voltage 50 V AC /70 V DC
Connection typeTerminals
Electromagnetic compatibilityNAMUR NE 21
CSA approvalCSA 16.70064204
Degree of protectionIEC/EN 60529
PROFIBUS DPPROFIBUS with RS-485 transmission technology

Comments