Pepperl+Fuchs KFD2-CD2-EX1
Current Driver

Pepperl+Fuchs KFD2-CD2-EX1
We ship to United States of America!

KFD2 CD2 EX1

  • Marking: space for marking on the front panel
  • Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial premises)
  • Degree of protection: IEC 60529:2001
  • Protection against electric shock: UL 61010-1:2004
  • Ambient temperature: -20...60 °C (-4...140 °F)
Item Number: KFD2-CD2-EX1
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview +
  • Comments +

Current Driver KFD2-CD2-EX1 is a single-channel isolated barrier designed for use in safety systems with explosive areas. It is used to transmit a 4-20 mA signal from a safe area to I/P converters, actuators and positioners located in hazardous areas.

Datasheet:

  • Signal type: Analog output
  • Safety Integrity Level (SIL): SIL 2
  • Connection: power bus or terminals 7+, 8-
  • Nominal voltage: 20...35 V DC
  • Ripple: within the permissible power range
  • Nominal current: current output: ≤ 50 mA; voltage output: ≤ 20 mA
  • Dissipated power: 1.2 W
  • Connection side: control side
  • Connection: terminals 9+, 10-, 11+
  • Voltage drop: additional current input: approx. 4 V at 20 mA
  • Input current: ≤ 100 µA at 50 °C (122 °F) at 10 V
  • Limit: Additional Current Input: Input Current: Approx. ≤40 mA. optional voltage input: input voltage: 12V DC
  • Transmission range: additional current input: 0...20 mA/additional voltage input: 0...10 V
  • Connection side: field side
  • Connection: terminals 1+, 2-
  • Voltage: additional current output: 17 V at 20 mA / additional voltage output: 0...10 V
  • Current: additional current output: 0...20 mA/additional voltage output: ≤ 20 mA
  • Load: additional current output: max. 850 ohms. additional voltage output: output resistance max. 3 ohms
  • Accuracy: 0.1%
  • Deviation: After calibration: ≤ ± 0.1% including non-linearity and hysteresis at 20 °C (68 °F)
  • Influence of ambient temperature: ≤ ± 0.01 %/K
  • Rise time: < 10 ms
  • Input/Power Supply: Functional Isolation, Rated Isolation Voltage 50V AC
  • Indicators: LED


Advantages:

  • Safety: Certified for use in hazardous area safety systems in accordance with ATEX, IECEx and CSA.
  • Reliability: The device has a robust construction and has been rigorously tested to ensure its reliability in the harshest environments.
  • Versatility: compatible with a wide range of I/P converters, actuators and positioners

Buy Pepperl+Fuchs KFD2-CD2-EX1 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. is a trusted online electrical distributor. Our catalog includes a comprehensive range of automation products from leading brands. We offer worldwide delivery and competitive pricing. Streamline your supply chain with our reliable services.