Pepperl+Fuchs KFD2-DU-Ex1.D
Switch Amplifier, Timer Relay

Pepperl+Fuchs KFD2-DU-Ex1.D
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Relay contact and transistor output
  • Adjustable output timer functions from 10 ms ... 60 min
  • Input frequency up to 80 Hz- pulse divider up to 1 kHz
  • Reset function
  • Configurable by keypad
  • Line fault detection (LFD)
Item Number: KFD2-DU-Ex1.D
485.38
-
+
Total price: 485.38
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
EU-Type Examination CertificateTГњV 99 ATEX 1408
Connection sidefield side
Power consumption1.8 W
Input Iacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Output II/resetbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output I, II against eachotherreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Connectionoutput I: terminals 10, 11, 12 ; output II: terminals 19+, 20-
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Degree of protectionIEC 60529:2001
UL approvalE223772
Input IIterminals 13+, 14- non-intrinsically safe
Control elementsControl panel
Input IIreset
Output IIsignal , electronic unit, isolated
Output Isignal , Relay output
CertificateTГњV 02 ATEX 1885 X
Labelingspace for labeling at the front
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Rated currentapprox. 100 mA
Rated voltage20 ... 30 V DC
Connection sidecontrol side
Input Iterminals 1+, 3-: Ex ia
Output IIterminals 19+, 20- non-intrinsically safe
Reset/power supply and collective errorfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
ConnectionInput I: terminals 1+, 3- ; input II: terminals 13+, 14-
ConnectionPower Rail or terminals 23+, 24-
Display elementsLEDs , display
Degree of protectionIP20
IECEx approvalIECEx TUN 03.0000
Output II/power supply and collective error basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Massapprox. 300 g
Output I/power supply and resetreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input I/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Connectionscrew terminals
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Configurationvia operating buttons
Output Iterminals 10, 11, 12 non-intrinsically safe
Electromagnetic compatibilityNE 21:2006
Signal typeDigital Input

Comments

No comments yet

Write a comment