Pepperl+Fuchs KFD2-EB2.SP
Power Feed Module
- Interface for Power Rail
- Supply current le- 4 A
- Replaceable fuse
- Relay contact output, reversible
- LED status indication
- Connection via spring terminals
Item Number:
KFD2-EB2.SP
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Output rated operating current | max. 4 A |
Contact loading | 30 V AC/ 2 A / cos andphi; 0.7 ; 40 V DC/ 2 A |
Optional accessories | - universal power rail UPR-03(-M)(-S) - universal power rail UPR-05(-S) - profile rail K-DUCT-GY(-UPR-03) - profile rail K-DUCT-GY(-UPR-05) - profile rail K-DUCT-BU(-UPR-03) - profile rail K-DUCT-BU(-UPR-05) |
Display elements | LEDs |
Degree of protection | IP20 |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Connection | Power Rail |
Certificate | PF 06 CERT 0916 X |
Configuration | via DIP switches |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
IECEx approval | IECEx UL 16.0051X |
Fusing | 5 A recommended maximum utilization of the fuse: 80 % |
Connection | terminals 11+, 12- terminals 8+, 9- |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Degree of protection | IEC 60529:2001 |
Rated voltage | 20 ... 30 V DC The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
Labeling | space for labeling at the front |
Connection | spring terminals |
Fault signal | relay output: NO contact |
Electromagnetic compatibility | NE 21:2006 |
Power dissipation | 1 W |
Mass | approx. 100 g |
Output voltage | 24 V DC |
Control elements | DIP-switch |
People also buy