Pepperl+Fuchs KFD2-GS-1.2W
Current/Voltage Trip Value

- 1-channel signal conditioner
- 24 V DC supply (Power Rail)
- Current and voltage input
- 2 relay contact outputs
- Programmable high/low alarm
- Configurable via DIP switches and potentiometer
- Terminal blocks with test sockets

Item Number:
KFD2-GS-1.2W
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Datasheet
- Alternative numbers
- Comments
Measurement rangeterminals 1+, 3-: voltage 0/1 ... 5 V, load 50 kandOmega; or voltage 0/2 ... 10 V, load 100 kandOmega;
terminals 2+, 3-: current 0/4 ... 20 mA ; load 50 andOmega;
Deviation | 1 % |
Rated voltage | 20 ... 30 V DC |
Degree of protection | IEC 60529 |
Connection side | field side |
Control elements | DIP-switch potentiometer |
Power consumption | < 1.5 W |
Output III | device configuration : terminals 4, 5, 6 |
Output I, II/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Signal type | Analog input |
Output I, II | terminals 7, 8, 9; 10, 11, 12 |
Degree of protection | IP20 |
Mass | approx. 120 g |
Connection | Power Rail or terminals 14+, 15- |
Labeling | space for labeling at the front |
Input/output I, II | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Connection side | control side |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 |
Rated current | < 50 mA |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input delay | 200 ms |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Connection | screw terminals |
Protection against electrical shock | EN 61010-1:2010 |
Configuration | via DIP switches via potentiometer |
Display elements | LEDs |