Pepperl+Fuchs KFD2-HLC-Ex1.D
HART Loop Converter
![Pepperl+Fuchs KFD2-HLC-Ex1.D](https://eltra-trade.com/files/products/pepperl/kfd2-hlc-ex1d.png)
We ship to United States of America!
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- HART field device input with transmitter power supply
- Usable as signal splitter (1 input and several outputs)
- 3 analog outputs 4 mA ... 20 mA
- Sink and source mode output
- Configurable by keypad
![](/files/brands/Pepperl+Fuchs-logo-brands.jpg)
Item Number:
KFD2-HLC-Ex1.D
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Connection sidefield side
Power dissipation | 2.3 W |
Mass | 300 g |
Configuration | via operating buttons via PACTware |
Current range | 4 ... 20 mA , (source or sink mode) |
Output I/II/III/power supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Connection | Power Rail or terminals 23+, 24- |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 |
Connection | output I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21 |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Signal type | Analog input |
Programming interface | programming socket |
Input resistance | 250 andOmega; , 5 % (terminals 2, 3 and with jumper on 5, 6) |
Connection | terminals 1, 2, 3, 4, 5, 6 |
Degree of protection | IEC 60529:2001 |
Output I, II, III | terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 non-intrinsically safe |
Certificate | PF 07 CERT 1142 X |
Control elements | Control panel |
Other outputs | HART communicator on terminals 22, 24 |
Equipment | terminals 1, 4/3 (with link between terminals 4 and 5) |
Rated voltage | 19 ... 30 V DC |
Connection side | control side |
Power consumption | 2.9 W |
Fault signal | downscale I 2 mA, upscale I 21.5 mA (acc. NAMUR NE43) or hold measurement value |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA |
Display elements | LEDs , display |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Output signal | analog |
Conformity | HART field device input (revision 5 to 7) |
Available voltage | 15.5 V at 20 mA, short-circuit protected |
Degree of protection | IP20 |
Labeling | space for labeling at the front |
Connection | screw terminals |
Electromagnetic compatibility | NE 21:2006 |
Rated current | approx. 120 mA at 24 V DC |
Collective error message | Power Rail and LED red |
Equipment | terminals 2, 5/3 |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Voltage range | 5 ... 30 V , sink mode from external supply |
Load | max. 650 andOmega; , source mode |
Buy Pepperl+Fuchs KFD2-HLC-Ex1.D with the best possible price and delivery terms on eltra-trade.com
eltra-trade.com offers electrical parts online. Our product range includes industrial sensors, motor control components, pneumatic automation, and many other automation equipment. We ship to any country as quickly as possible. By providing you with minimum prices, you can save money. You will be pleased to work with us. Our clients include a large number of well-known global manufacturing companies.
People also buy
Comments
No comments yet