Pepperl+Fuchs KFD2-HLC-Ex1.D
HART Loop Converter

Pepperl+Fuchs KFD2-HLC-Ex1.D
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • HART field device input with transmitter power supply
  • Usable as signal splitter (1 input and several outputs)
  • 3 analog outputs 4 mA ... 20 mA
  • Sink and source mode output
  • Configurable by keypad
Item Number: KFD2-HLC-Ex1.D
573.00
-
+
Total price: 573.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Connection sidefield side

Power dissipation2.3 W
Mass300 g
Configurationvia operating buttons
via PACTware
Current range4 ... 20 mA , (source or sink mode)
Output I/II/III/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
ConnectionPower Rail or terminals 23+, 24-
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
EU-Type Examination CertificateBASEEFA 07 ATEX 0174
Connectionoutput I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Signal typeAnalog input
Programming interfaceprogramming socket
Input resistance250 andOmega; , 5 % (terminals 2, 3 and with jumper on 5, 6)
Connectionterminals 1, 2, 3, 4, 5, 6
Degree of protectionIEC 60529:2001
Output I, II, IIIterminals 7, 8, 9; 13, 14, 15; 19, 20, 21 non-intrinsically safe
CertificatePF 07 CERT 1142 X
Control elementsControl panel
Other outputsHART communicator on terminals 22, 24
Equipmentterminals 1, 4/3 (with link between terminals 4 and 5)
Rated voltage19 ... 30 V DC
Connection sidecontrol side
Power consumption2.9 W
Fault signaldownscale I 2 mA, upscale I 21.5 mA (acc. NAMUR NE43) or hold measurement value
Open circuit voltage/short-circuit currenttyp. 24 V / 28 mA
Display elementsLEDs , display
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Output signalanalog
ConformityHART field device input (revision 5 to 7)
Available voltage15.5 V at 20 mA, short-circuit protected
Degree of protectionIP20
Labelingspace for labeling at the front
Connectionscrew terminals
Electromagnetic compatibilityNE 21:2006
Rated currentapprox. 120 mA at 24 V DC
Collective error messagePower Rail and LED red
Equipmentterminals 2, 5/3
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Voltage range5 ... 30 V , sink mode from external supply
Loadmax. 650 andOmega; , source mode

Comments

No comments yet

Write a comment