Pepperl+Fuchs KFD2-HLC-Ex1.D.2W
HART Loop Converter

Pepperl+Fuchs KFD2-HLC-Ex1.D.2W
We ship to United States of America!
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • HART field device input with transmitter power supply
  • Usable as signal splitter (1 input and several outputs)
  • 2 relay contact outputs (change-over contacts)
  • 3 analog outputs 4 mA ... 20 mA
  • Sink and source mode output
  • Configurable by keypad
Item Number: KFD2-HLC-Ex1.D.2W
513.96
-
+
Total price: 513.96
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
  • Overview +
  • Comments +
Connection sidefield side
Connectionoutput I: terminals 10, 11, 12, output II: terminals 16, 17, 18
output III: terminals 7, 8, 9, output IV: terminals 13, 14, 15, output V: terminals 19, 20, 21
Available voltage 15.5 V at 20 mA, short-circuit protected
Mass300 g
Ambient temperature-20 ... 60 ?°C (-4 ... 140 ?°F)
Equipmentterminals 1, 4/3 (with link between terminals 4 and 5)
Connection sidecontrol side
Output I/IIfunctional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Display elementsLEDs , display
Electromagnetic compatibilityNE 21:2006
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Power dissipation2.5 W
ConformityHART field device input (revision 5 to 7)
EU-Type Examination CertificateBASEEFA 07 ATEX 0174
Labelingspace for labeling at the front
Power consumption3.1 W
Degree of protectionIP20
Equipmentterminals 2, 5/3
Signal typeAnalog input
ConnectionPower Rail or terminals 23+, 24-
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Connectionscrew terminals
Relayprogrammable either for fault or trip value (with direction, hysteresis and delay)
CertificatePF 07 CERT 1141 X
Degree of protectionIEC 60529:2001
Output I, IIterminals 10, 11, 12; 16, 17, 18 , non-intrinsically safe
Rated voltage19 ... 30 V DC
Connectionterminals 1, 2, 3, 4, 5, 6
Control elementsControl panel
Configurationvia operating buttons
via PACTware
Collective error messagePower Rail and LED red
Programming interfaceprogramming socket
Output III/IV/V/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Open circuit voltage/short-circuit currenttyp. 24 V / 28 mA
Other outputsHART communicator on terminals 22, 24
Rated currentapprox. 130 mA at 24 V DC
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Input resistance250 andOmega; , 5 % (terminals 2, 3 and with jumper on 5, 6)
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Output III, IV, Vterminals 7, 8, 9; 13, 14, 15; 19, 20, 21 , non-intrinsically safe
Output I, II/other circuitsreinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms

Buy Pepperl+Fuchs KFD2-HLC-Ex1.D.2W with the best possible price and delivery terms on eltra-trade.com

Make electrical parts online shopping with eltra-trade.com. Our product catalog includes a lot of items of automation equipment: motor control components, industrial sensors, pneumatic automation, low voltage products, and others. You can receive your order in any country in the world. By purchasing from our company, you receive quality products at low prices. We always reply very fast to requests from our customers. Among our customers are plenty of known world industrial companies.

Comments

No comments yet

Write a comment