Pepperl+Fuchs KFD2-HLC-Ex1.D.2W
HART Loop Converter
We ship to United States of America!
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- HART field device input with transmitter power supply
- Usable as signal splitter (1 input and several outputs)
- 2 relay contact outputs (change-over contacts)
- 3 analog outputs 4 mA ... 20 mA
- Sink and source mode output
- Configurable by keypad
Item Number:
KFD2-HLC-Ex1.D.2W
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
The price and delivery terms is not final. Please check with the manager.
Contact our experts
- Overview +
- Comments +
Connection side | field side |
Connection | output I: terminals 10, 11, 12, output II: terminals 16, 17, 18 output III: terminals 7, 8, 9, output IV: terminals 13, 14, 15, output V: terminals 19, 20, 21 |
Available voltage | 15.5 V at 20 mA, short-circuit protected |
Mass | 300 g |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Equipment | terminals 1, 4/3 (with link between terminals 4 and 5) |
Connection side | control side |
Output I/II | functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff |
Display elements | LEDs , display |
Electromagnetic compatibility | NE 21:2006 |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
Power dissipation | 2.5 W |
Conformity | HART field device input (revision 5 to 7) |
EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 |
Labeling | space for labeling at the front |
Power consumption | 3.1 W |
Degree of protection | IP20 |
Equipment | terminals 2, 5/3 |
Signal type | Analog input |
Connection | Power Rail or terminals 23+, 24- |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Connection | screw terminals |
Relay | programmable either for fault or trip value (with direction, hysteresis and delay) |
Certificate | PF 07 CERT 1141 X |
Degree of protection | IEC 60529:2001 |
Output I, II | terminals 10, 11, 12; 16, 17, 18 , non-intrinsically safe |
Rated voltage | 19 ... 30 V DC |
Connection | terminals 1, 2, 3, 4, 5, 6 |
Control elements | Control panel |
Configuration | via operating buttons via PACTware |
Collective error message | Power Rail and LED red |
Programming interface | programming socket |
Output III/IV/V/power supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA |
Other outputs | HART communicator on terminals 22, 24 |
Rated current | approx. 130 mA at 24 V DC |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Input resistance | 250 andOmega; , 5 % (terminals 2, 3 and with jumper on 5, 6) |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Output III, IV, V | terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 , non-intrinsically safe |
Output I, II/other circuits | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms |
Buy Pepperl+Fuchs KFD2-HLC-Ex1.D.2W with the best possible price and delivery terms on eltra-trade.com
Make electrical parts online shopping with eltra-trade.com. Our product catalog includes a lot of items of automation equipment: motor control components, industrial sensors, pneumatic automation, low voltage products, and others. You can receive your order in any country in the world. By purchasing from our company, you receive quality products at low prices. We always reply very fast to requests from our customers. Among our customers are plenty of known world industrial companies.
People also buy
Comments
No comments yet