Pepperl+Fuchs KFD2-HLC-Ex1.D.4S
HART Loop Converter

Pepperl+Fuchs KFD2-HLC-Ex1.D.4S
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • HART field device input with transmitter power supply
  • Usable as signal splitter (1 input and several outputs)
  • 4 relay contact outputs (NO contact)
  • 3 analog outputs 4 mA ... 20 mA
  • Sink and source mode output
  • Configurable by keypad
Item Number: KFD2-HLC-Ex1.D.4S
769.77
-
+
Total price: 769.77
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Equipmentterminals 1, 4/3 (with link between terminals 4 and 5)
Power dissipation2.7 W
Configurationvia operating buttons
via PACTware
Labelingspace for labeling at the front
ConnectionPower Rail or terminals 23+, 24-
Output I, II/III, IVfunctional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Output V/VI/VII/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Connection sidefield side
Equipmentterminals 2, 5/3
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
ConformityHART field device input (revision 5 to 7)
Rated voltage19 ... 30 V DC
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
EU-Type Examination CertificateBASEEFA 07 ATEX 0174
Connectionterminals 1, 2, 3, 4, 5, 6
Output I, II, III, IV/other circuitsreinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms
Signal typeAnalog input
Output V, VI, VIIterminals 7, 8, 9; 13, 14, 15; 19, 20, 21 , non-intrinsically safe
Control elementsControl panel
Input resistance250 andOmega; , 5 % (terminals 2, 3 and with jumper on 5, 6)
Connectionoutput I: terminals 10, 11, output II: terminals 11, 12, output III: terminals 16, 17, output IV: terminals 17, 18
output V: terminals 7, 8, 9, output VI: terminals 13, 14, 15, output VII: terminals 19, 20, 21
Other outputsHART communicator on terminals 22, 24
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Connectionscrew terminals
Connection sidecontrol side
Relayprogrammable either for fault or trip value (with direction, hysteresis and delay)
Display elementsLEDs , display
Rated currentapprox. 140 mA at 24 V DC
Electromagnetic compatibilityNE 21:2006
Mass300 g
CertificatePF 07 CERT 1141 X
Output I, II, III, IVterminals 10, 11; 11, 12; 16, 17; 17, 18 , non-intrinsically safe
Degree of protectionIP20
Power consumption3.3 W
Open circuit voltage/short-circuit currenttyp. 24 V / 28 mA
Collective error messagePower Rail and LED red
Programming interfaceprogramming socket
Degree of protectionIEC 60529:2001
Available voltage 15.5 V at 20 mA, short-circuit protected
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)

Comments

No comments yet