Pepperl+Fuchs KFD2-HMM-16
HART Multiplexer Master kfd2 hmm 16

Pepperl+Fuchs KFD2-HMM-16
  • 16-channel
  • 24 V DC supply (Power Rail)
  • HART field device input (revision 5 to 7)
  • Up to 15 KFD0-HMS-16 slave units can be connected
  • Up to SIL3 acc. to IEC 61508
Item Number: KFD2-HMM-16
1398.00
-
+
Total price: 1398.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Output voltage400 mV ss(with the terminator resistance specified above)

Connectionterminals 17+, 18-
Output resistance100 andOmega; or smaller, capacitive coupling
Safety Integrity Level (SIL)SIL 3
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Power consumptionmax. 3 W
TypeRS-485 , 2-wire multidrop
Degree of protectionIP20
Transfer rate9600, 19200, or 38400 Bit/s (selectable with DIL switch (2 and 3) by the user)
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Control elementsDIP-switch
Massapprox. 250 g
Input voltage range0.08 ... 4 V ss ; typ. В± 5.2 V as local reference
Degree of protectionIEC 60529:2001
CertificatePF 07 CERT 1143 X
Labelingspace for labeling at the front
Connection26-pin flat cable for analog connections
14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16
Leakage current< 3 andmicro;A at -20 ... 85 В°C (-4 ... 185 В°F)
Address selectionOne of 31 possible addresses selectable per DIL switch (4 ... 8)
Configurationvia DIP switches
Terminating resistorexternal 230 ... 500 andOmega; standard (up to 1000 andOmega; possible)
Rated voltage20 ... 32 V DC typical at 100 mA
Dimensions40 x 107 x 115 mm (1.6 x 4.2 x 4.5 inch) , housing type C1
Input impedanceaccording to HART specification
ConformityHART field device input (revision 5 to 7)

Comments

No comments yet

Write a comment