Pepperl+Fuchs KFD2-PT2-Ex1
Potentiometer Converter

Pepperl+Fuchs KFD2-PT2-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Potentiometer input
  • Voltage output 0 V ... 10 V
  • Lead resistance compensation adjustment
  • Accuracy 0.05 %
  • Up to SIL 2 acc. to IEC 61508
Item Number: KFD2-PT2-Ex1
409.00
-
+
Total price: 409.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Voltage output0 ... 10 V
Connectionscrew terminals
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Lead resistance5 % of the potentiometer resistance (adjustable)
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Ripplewithin the supply tolerance
Configurationvia potentiometer
Electromagnetic compatibilityNE 21:2006
Massapprox. 120 g
Connectionterminals 4-, 5-, 3+, 2+, 1+
CertificateTГњV 02 ATEX 1797 X
Output resistancemax. 30 andOmega;
EU-Type Examination CertificateBAS 00 ATEX 7171
Signal typeAnalog input
Rated voltage20 ... 35 V DC
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Connection sidecontrol side
Connectionterminals 7-, 8+
Degree of protectionIP20
Degree of protectionIEC 60529:2001
Accuracy0.05 %
Protection against electrical shockUL 61010-1
Connection sidefield side
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Control elementspotentiometer
ConnectionPower Rail or terminals 11+, 12-
Rise time10 to 90 % 8 ms; 10 to 90 % within 1 % of span 25 ms
Power dissipation0.5 W
Power consumption0.6 W
Safety Integrity Level (SIL)SIL 2
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)

Comments

No comments yet