  • 1-channel signal conditioner
  • 24 V DC supply
  • Logic input 19 V DC ... 26.4 V DC
  • Recommended connectable voltage 50 V AC ... 230 V AC, 60 V DC ... 110 V DC
  • Relay contact output for de-energized to safe function
  • Line fault transparency (LFT)
  • Diagnostic function
  • Up to SIL 3 acc. to IEC 61508
  • Up to PL e acc. to EN/ISO 13849
Item Number: KFD2-RSH-1.2D.FL3
416.16
-
+
Total price: 416.16
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Line fault detectionlow voltage < 35 V AC
undercurrent: 10 mA AC; overcurrent: 5.5 A AC (relay energized)
breakage: 48 kandOmega;; short-circuit: 29 andOmega; (load, relay de-energized)
Power consumption< 1.7 W , includes the power consumption of the digital input , see derating curves
Safety Integrity Level (SIL)SIL 3
Mechanical life5 x 106 switching cycles
Connectionterminals 10, 11
Pulse/Pause ratiomin. 150 ms / min. 150 ms with disabled internal fault detection
min. 1 s / min. 1 s with enabled internal fault detection
Display elementsLEDs
Connection sidecontrol side
Signal typeDigital Output
Contact loading253 V AC/5 A/cos andphi; 0.7; 30 V DC/5 A resistive load , see derating curves
Labelingspace for labeling at the front
Reaction time< 2 s
Connectionterminals 7+, 8-
Control elementsDIP-switch
Degree of protectionIEC 60529:2013
Switching frequency< 3 Hz with disabled internal fault detection
< 0.5 Hz with enabled internal fault detection
Configurationvia DIP switches
Connectable voltage50 ... 230 V AC
60 ... 110 V DC
Power dissipation< 3.3 W at 5 A , see derating curves
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Input/fault indication outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 30 Veff
Performance level (PL)PL e
Fuse rating2.5 A (scope of delivery)
max. 5 AT, recommended maximum utilization of the fuse: 80 %
Rated current0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: 36 mA (minimum load current DO card)
Inrush current< 200 mA after 100 micro/s
ConnectionPower Rail or terminals 14+, 15-
Degree of protectionIP20
Minimum switch current10 mA
Connection sidefield side
Electromagnetic compatibilityNE 21:2012 , EN 61326-3-2:2008 , EN 61326-3-1:2008
Connectionscrew terminals
Input current35 mA at 24 V DC , max. 44 mA at 19 V DC , with enabled internal fault detection
Test pulse lengthmax. 2 ms from DO card
Rated voltage19 ... 26.4 V DC
Massapprox. 142 g
Contact loading30 V DC/ 0.5 A resistive load
Connectionexternal voltage : terminals 4+, 5+, 2-
load : terminals 6, 3
Mechanical life105 switching cycles
Signal level0-signal: -5 ... 5 V DC
1-signal: 19 ... 26.4 V DC
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Observe the temperature range limited by derating, see section derating.
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Output/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff