  • 1-channel signal conditioner
  • 24 V DC supply
  • Logic input 19 V DC ... 26.4 V DC
  • Recommended connectable voltage 8 V DC ... 60 V DC
  • Relay contact output for energized to safe function
  • Line fault transparency (LFT)
  • Diagnostic function
  • Up to SIL 3 acc. to IEC 61508
Item Number: KFD2-RSH-1.2E.L2
416.16
-
+
Total price: 416.16
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Connection sidecontrol side
Electromagnetic compatibilityNE 21:2012 , EN 61326-3-2:2008 , EN 61326-3-1:2008
Connectable voltage8 ... 60 V DC
Massapprox. 134 g
Display elementsLEDs
Protection against electrical shockEN 61010-1:2010
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Mechanical life5 x 106 switching cycles
Line fault detectionlow voltage < 5 V DC
undercurrent: 10 mA DC; overcurrent: 2.2 A DC (relay energized)
breakage: 8.2 kandOmega;; short-circuit: 11 andOmega; (load, relay de-energized)
Connection sidefield side
Output/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Rated voltage19 ... 26.4 V DC
Reaction time< 2 s
Input current35 mA at 24 V DC , max. 44 mA at 19 V DC , with enabled internal fault detection
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Configurationvia DIP switches
Degree of protectionIEC 60529:2013
CertificatePF 17 CERT 4305 X
Contact loading30 V DC / 5 A resistive load , see derating curves
Signal typeDigital Output
Connectionscrew terminals
Connectionexternal voltage : terminals 5+, 2-
load : terminals 6, 3
Power dissipation< 3.3 W at 5 A , see derating curves
Mechanical life105 switching cycles
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Observe the temperature range limited by derating, see section derating.
Power consumption< 1.7 W , includes the power consumption of the digital input , see derating curves
Connectionterminals 10, 11
Contact loading30 V DC/ 0.5 A resistive load
Switching frequency< 3 Hz with disabled internal fault detection
< 0.5 Hz with enabled internal fault detection
Safety Integrity Level (SIL)SIL 3
Test pulse lengthmax. 2 ms from DO card
Rated current0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: 36 mA (minimum load current DO card)
Degree of protectionIP20
Inrush current< 200 mA after 100 micro/s
Fuse rating2.5 A (scope of delivery)
max. 5 AT, recommended maximum utilization of the fuse: 80 %
Pulse/Pause ratiomin. 150 ms / min. 150 ms with disabled internal fault detection
min. 1 s / min. 1 s with enabled internal fault detection
ConnectionPower Rail or terminals 14+, 15-
Signal level0-signal: -5 ... 5 V DC
1-signal: 19 ... 26.4 V DC
Labelingspace for labeling at the front
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Connectionterminals 7+, 8-
Minimum switch current10 mA
Input/fault indication outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 30 Veff
Control elementsDIP-switch

Buy Pepperl+Fuchs KFD2-RSH-1.2E.L2 with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. delivers top-quality industrial control products. Our extensive inventory ensures you find the parts you need, with worldwide delivery options. We offer competitive prices and personalized service. Get in touch today to see how we can support your business effectively and efficiently.