Pepperl+Fuchs KFD2-SCD-Ex1.LK
SMART Current Driver

Pepperl+Fuchs KFD2-SCD-Ex1.LK
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Current output up to 700 Omega- load
  • HART I/P and valve positioner
  • Line fault detection (LFD)
  • Accuracy 0.1 %
  • Terminal blocks with test sockets
  • Up to SIL 2 acc. to IEC 61508
Item Number: KFD2-SCD-Ex1.LK
471.85
-
+
Total price: 471.85
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
KFD2-SCD-EX1.LK art 223998

EU-Type Examination CertificateBAS 00 ATEX 7215

Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Connectionterminals 1+, 2-
Connection sidefield side
Insulation coordinationEN 50178:1997
Labelingspace for labeling at the front
Load100 ... 700 andOmega;
Degree of protectionIEC 60529:2001
Power consumption1.3 W
CertificateTГњV 99 ATEX 1499 X
Massapprox. 100 g
Current4 ... 20 mA
Dimensions20 x 115 x 115 mm (0.8 x 4.5 x 4.5 inch) , housing type B1
Connection sidecontrol side
Current4 ... 20 mA limited to approx. 25 mA
Safety Integrity Level (SIL)SIL 2
Connectionterminals 7-, 8+
Ripplewithin the supply tolerance
Voltage dropapprox. 4 V or internal resistance 200 andOmega; at 20 mA
Electromagnetic compatibilityNE 21:2006
Rated voltage20 ... 35 V DC
Power dissipation1.1 W at 20 mA into 10 V (equivalent to 500 andOmega;) load
Input resistance> 100 kandOmega;, when wiring resistance in the field < 50 andOmega; or > 800 andOmega; at 20 mA
Voltage14 V at 20 mA
Galvanic isolationEN 50178:1997
Rise time< 100 micro/s at bounce from 10 ... 90 %
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
IECEx approvalIECEx BAS 16.0045
Degree of protectionIP20
Accuracy0.1 %
Connectionscrew terminals
ConnectionPower Rail or terminals 11+, 12-
Signal typeAnalog output
Display elementsLEDs

Comments

No comments yet