Pepperl+Fuchs KFD2-SCD2-Ex1.LK
SMART Current Driver

Pepperl+Fuchs KFD2-SCD2-Ex1.LK
We ship to United States of America!
  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

Item Number: KFD2-SCD2-Ex1.LK
405.40
-
+
Total price: 405.40
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
  • Degree of protectionIEC 60529

  • Current output up to 650 &Omega- load

  • HART I/P and valve positioner

  • Line fault detection (LFD)

  • Accuracy 0.1 %

  • Up to SIL 2 acc. to IEC 61508

Rated voltage

19 ... 30 V DC

Mounting

on 35 mm DIN mounting rail acc. to EN 60715:2001

Voltage

≥ 13 V at 20 mA

Safety Integrity Level (SIL)

SIL 2

Rise time

10 to 90 % ≤ 10 ms

Accuracy

0.1 %

Electromagnetic compatibility

NE 21:2012

EN 61326-3-2:2008

Frequency range

field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)

control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)

Connection side

field side

Connection

terminals 1+, 2-

terminals 3+, 2- (no short circuit detection)

Signal type

Analog output

Deviation

at 20 В°C (68 В°F), 4 ... 20 mA

< 0.1 % of full scale, incl. non-linearity and hysteresis

Supplementary information

Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Degree of protection

IP20

Protection against electrical shock

UL 61010-1:2012

Power consumption

≤ 700 mW

Input voltage

open loop voltage of the control system ≤ 30 V

Labeling

space for labeling at the front

Dimensions

20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2

Display elements

LEDs

Output/power supply

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Optional accessories

- power feed module KFD2-EB2(.R4A.B)(.SP)

- universal power rail UPR-03(-M)(-S)

- profile rail K-DUCT-BU(-UPR-03)

UL approval

E106378

Connection

screw terminals

Input resistance

field wiring open circuit : > 100 kΩ

field wiring < 50 Ω : > 100 kΩ when using terminals 1 and 2

Connection

Power Rail or terminals 14+, 15-

Load

100 ... 650 Ω , for terminals 1, 2

0 ... 550 Ω , for terminals 2, 3

Mass

approx. 115 g

Current

4 ... 20 mA

Ambient temperature

-40 ... 70 В°C (-40 ... 158 В°F)

EU-type examination certificate

BAS 00 ATEX 7240 X

Rated current

≤ 30 mA at 24 V

Input/Output

basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Voltage drop

approx. 6 V at 20 mA

Input signal

4 ... 20 mA , limited to approx. 30 mA

Ripple

20 mV rms

Certificate

TГњV 99 ATEX 1499 X

Connection

terminals 7-, 8+, (9+)

Connection side

control side

Ripple

≤ 10 %

Power dissipation

≤ 600 mW at 20 mA and 500 Ω load

Input/power supply

basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff


Buy Pepperl+Fuchs KFD2-SCD2-Ex1.LK with the best possible price and delivery terms on eltra-trade.com

Eltra Trade s.r.o. is a trusted industrial automation supplier. We offer a vast selection of products from renowned manufacturers. Worldwide delivery is available, ensuring you receive your order promptly. Competitive prices and exceptional service are our priorities. Experience the benefits of partnering with us for your automation needs.