Pepperl+Fuchs KFD2-SCD2-Ex2.LK
SMART Current Driver

Pepperl+Fuchs KFD2-SCD2-Ex2.LK
We ship to United States of America!
  • 2-channel isolated barrier

  • 24 V DC supply (Power Rail)

Item Number: KFD2-SCD2-Ex2.LK
Price on Request
-
+
Total price: 0.00
Contact our experts
  • Overview +
  • Comments +
  • Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001

  • Current output up to 650 &Omega- load

  • HART I/P and valve positioner

  • Line fault detection (LFD)

  • Accuracy 0.1 %

  • Up to SIL 2 acc. to IEC 61508

Power dissipation

≤ 1 W at 20 mA and 500 Ω load

Current

4 ... 20 mA

Accuracy

0.1 %

Connection side

control side

Connection

terminals 1+, 2-; 4+, 5-

terminals 3+, 2-; 6+, 5- (no short circuit detection)

Voltage drop

approx. 6 V at 20 mA

Certificate

T??V 99 ATEX 1499 X

Degree of protection

IEC 60529

Rated current

≤ 60 mA at 24 V

Display elements

LEDs

Supplementary information

Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Rated voltage

19 ... 30 V DC

Input resistance

field wiring open circuit : > 100 kΩ

field wiring < 50 Ω : > 100 kΩ when using terminals 1, 2 and 4, 5

Connection

screw terminals

Safety Integrity Level (SIL)

SIL 2

Degree of protection

IP20

Input signal

4 ... 20 mA , limited to approx. 30 mA

EU-type examination certificate

BAS 00 ATEX 7240 X

Mass

approx. 135 g

Load

100 ... 650 Ω , for terminals 1, 2; 4, 5

0 ... 550 Ω , for Terminals 2, 3; 5, 6

Power consumption

≤ 1.2 W

Rise time

10 to 90 % ≤ 10 ms

Ambient temperature

-40 ... 70 ?°C (-40 ... 158 ?°F)

Input/input

functional insulation, rated insulation voltage 50 V AC

Protection against electrical shock

UL 61010-1:2012

Input voltage

open loop voltage of the control system ≤ 30 V

Ripple

20 mV rms

Electromagnetic compatibility

NE 21:2012

EN 61326-3-2:2008

Input/Output

basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Dimensions

20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2

UL approval

E106378

Frequency range

field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)

control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)

Input/power supply

basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Signal type

Analog output

Connection

terminals 7-, 8+, (9+); 10-, 11+, (12+)

Voltage

≥ 13 V at 20 mA

Deviation

at 20 ?°C (68 ?°F), 4 ... 20 mA

< 0.1 % of full scale, incl. non-linearity and hysteresis

Ripple

≤ 10 %

Connection side

field side

Output/power supply

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Labeling

space for labeling at the front

Connection

Power Rail or terminals 14+, 15-

Optional accessories

- power feed module KFD2-EB2(.R4A.B)(.SP)

- universal power rail UPR-03(-M)(-S)

- profile rail K-DUCT-BU(-UPR-03)


Buy Pepperl+Fuchs KFD2-SCD2-Ex2.LK with the best possible price and delivery terms on eltra-trade.com

eltra-trade.com provides top-quality industrial control components. Our online catalog features a wide range of products to meet your specific requirements. Enjoy the convenience of consolidated shipments and competitive pricing. Join our satisfied customers who rely on us for their automation solutions.

Comments

No comments yet

Write a comment