Pepperl+Fuchs KFD2-SH-Ex1.T.OP
Switch Amplifier

Pepperl+Fuchs KFD2-SH-Ex1.T.OP
  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

Item Number: KFD2-SH-Ex1.T.OP
671.35
-
+
Total price: 671.35
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Datasheet
  • Alternative numbers
  • PDF
  • Comments
  • Input for approved dry contacts or SN/S1N sensors

  • Active voltage output

  • Relay contact output

  • Fault indication output

  • Line fault detection (LFD)

  • Up to SIL 3 acc. to IEC 61508

  • Up to PL d acc. to EN/ISO 13849

Safety Integrity Level (SIL)SIL 3
Rated current≤ 100 mA
Signal typeDigital Input
Ripple≤ 10 %
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Electromagnetic compatibilityNE 21:2011
ConnectionPower Rail
Labelingspace for labeling at the front
Power dissipation1.5 W
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Degree of protectionIEC 60529:2001
Connection sidecontrol side
Power consumptionmax. 1.7 W
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Response delay≤ 1 ms
SafetyIEC/EN 61508:2010
Connectionterminals 4+, 6-
Output Iactive voltage output, short-circuit proof
0-signal: 0 V
1-signal: 20 ... 31 V DC at max. 15 mA
fault: 0 V
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
CertificateTГњV 99 ATEX 1493 X
Display elementsLEDs
Lead resistancemax. 50 Ω , cable capacitances and inductances must be observed in hazardous areas
Output IIIrelay , fault signal
Open circuit voltage/short-circuit currentapprox. 8.4 V DC / approx. 11.7 mA
Rated voltage20 ... 30 V DC
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Connection sidefield side
Performance level (PL)PL d
Massapprox. 150 g
Connectionoutput I: terminals 7+, 8- ; output II: terminals 9, 10 ; output III: terminals 11, 12
Degree of protectionIP20
EU-type examination certificatePTB 00 ATEX 2041
Connectionscrew terminals
Output IIrelay

Comments

No comments yet

Write a comment