Pepperl+Fuchs KFD2-SL2-Ex1.LK
Solenoid Driver

Pepperl+Fuchs KFD2-SL2-Ex1.LK
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Output 45 mA at 11.2 V DC
  • Logic input, non-polarized
  • Fault indication output
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508
Item Number: KFD2-SL2-Ex1.LK
408.60
-
+
Total price: 408.60
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Rated voltage19 ... 30 V DC

Safety Integrity Level (SIL)SIL 2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
ConnectionPower Rail or terminals 14+, 15-
Output I, II against eachotherreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Configurationvia DIP switches
Connectionterminals 7, 8
Connection sidecontrol side
Degree of protectionIP20
Output IIfault signal
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Control elementsDIP-switch
Electromagnetic compatibilityNE 21:2007
Labelingspace for labeling at the front
EU-Type Examination CertificateZELM 99 ATEX 0015
Signal level1-signal: 16 ... 30 V DC
0-signal: 0 ... 5 V DC
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Massapprox. 150 g
Power consumptionmax. 2 W at 45 mA output current
CertificateTГњV 02 ATEX 1820 X
Output II/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Connectionscrew terminals
Input currentapprox. 3 mA
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Degree of protectionIEC 60529:2001
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Display elementsLEDs
Connection sidefield side
Signal typeDigital Output
Power dissipationmax. 1.5 W

Comments

No comments yet