Pepperl+Fuchs KFD2-SLD-Ex1.13100
Solenoid Driver

Pepperl+Fuchs KFD2-SLD-Ex1.13100
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Logic input
  • Output 100 mA at 13 V DC
  • Alternating outputs for the operation of solenoids with 2 coils
  • High output power for IIB gas group
  • Line fault transparency (LFT)
  • Test pulse immunity
  • Up to SIL 3 acc. to IEC 61508
Item Number: KFD2-SLD-Ex1.13100
444.00
-
+
Total price: 444.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
channel 2: terminals 10+, 11-
Connectionscrew terminals
Degree of protectionIEC 60529:2001
Protection against electrical shockEN 61010-1:2010
Switching frequencymax. 2 Hz
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Voltage 13 V
Rated voltage19 ... 30 V DC
loop powered
Connection sidecontrol side
Signal typeDigital Output
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Power dissipation1.5 W at 24 V , 130 andOmega; load
Input/inputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Open loop voltagetyp. 19.2 V
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Massapprox. 200 g
Energized/De-energized delay30 ms / 30 ms
Loadnominal 0.08 ... 1 kandOmega;
Input currentapprox. 6 mA at 24 V DC
Connection sidefield side
Internal resistorapprox. 64 andOmega;
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
IECEx approvalIECEx EXA 17.0019X
Configurationvia DIP switches
Electromagnetic compatibilityNE 21:2011
For further information see system description.
Degree of protectionIP20
Currenttyp. 100 mA
Current limit105 mA
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Safety Integrity Level (SIL)SIL 3
EU-Type Examination CertificateEXA 17 ATEX 0076X
ConnectionPower Rail or terminals 14+, 15-
Connectionchannel 1: terminals 1+, 2-, 3
channel 2: terminals 4+, 5-, 6-
Display elementsLEDs
Line fault detectionsignal at short-circuit RB < 30 andOmega;, lead breakage RB > 10 kandOmega; ,
test current < 4 mA pulsing (20 ms On, 200 ms Off)
Output/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Input current115 mA at 24 V , 130 andOmega; load
Output/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Signal level1-signal: 15 ... 30 V DC
0-signal: 0 ... 5 V DC
Labelingspace for labeling at the front
Control elementsDIP-switch
Connectionchannel 1: terminals 7+, 8-

Comments

No comments yet

Write a comment