Pepperl+Fuchs KFD2-SOT2-Ex2.IO-Y181008
Switch Amplifier
- 2-channel isolated barrier
- 24 V DC supply (Power Rail)
- Dry contact or NAMUR inputs
- Isolated passive transistor output, TTL level
- Line fault detection (LFD)
- Reversible mode of operation
Item Number:
KFD2-SOT2-Ex2.IO-Y181008
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Ripple | 10 % |
Configuration | via DIP switches |
Rated voltage | 20 ... 30 V DC |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) |
Degree of protection | IEC 60529:2001 |
Signal level | 1-signal: switching voltage - 0.85 V max. at 2 mA switching current 0-signal: switched off (off-state current 10 andmicro;A) |
Input/Output | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Output/power supply | basic insulation according to IEC 62103, rated insulation voltage 50 Veff |
Connection | screw terminals |
Certificate | TГњV 99 ATEX 1499 X |
Electromagnetic compatibility | NE 21:2004 |
Display elements | LEDs |
Control elements | DIP-switch |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
Switching voltage | max. 30 V |
Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
Switching frequency | 5 kHz |
Rated current | 50 mA |
EU-Type Examination Certificate | PTB 00 ATEX 2035 |
Collective error message | Power Rail |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Mass | approx. 150 g |
Connection side | field side |
Switching current | max. 2 mA , short-circuit protected |
EU-Type Examination Certificate | DMT 01 ATEX E 133 |
Input | EN 60947-5-6:2000 |
Degree of protection | IP20 |
Connection side | control side |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data |
Input/power supply | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms |
Output I, II | signal , TTL compatible |
Connection | output I: terminals 7+, 8- ; output II: terminals 10+, 11- |
Labeling | space for labeling at the front |
Signal type | Digital Input |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Line fault detection | breakage I 0.1 mA , short-circuit I > 6 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Galvanic isolation | IEC 62103:2003 |
Connection | Power Rail or terminals 14+, 15- |
Output/Output | basic insulation according to IEC 62103, rated insulation voltage 50 Veff |