Pepperl+Fuchs KFD2-SR2-Ex1.W
Switch Amplifier
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Overview +
- Comments +
kfd2 sr2 ex1w is a signal conditioner or isolated barrier from Pepperl+Fuchs. It isolates and converts signals to prevent interference, allowing safe and efficient data transmission in hazardous locations.
Datasheet:
- Pulse/Pause ratiomin. 20 ms / min. 20 ms
- Dry contact or NAMUR inputs
- Relay contact output
- Line fault detection (LFD)
- Reversible mode of operation
- Up to SIL 2 acc. to IEC 61508/IEC 61511
Electromagnetic compatibility | NE 21:2006 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Output | signal ; relay |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Certificate | PF 08 CERT 0803 |
Switching frequency | < 10 Hz |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Connection | terminals 1+, 2+, 3- |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Power dissipation | 0.7 W |
Labeling | space for labeling at the front |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Input | Ex ic |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Power consumption | < 0.9 W |
Input | EN 60947-5-6:2000 |
Connection | screw terminals |
Minimum switch current | 2 mA / 24 V DC |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Connection | terminals 7, 8, 9 |
Connection side | field side |
Mechanical life | 107 switching cycles |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Degree of protection | IP20 |
Connection | Power Rail or terminals 14+, 15- |
Connection side | control side |
Signal type | Digital Input |
IECEx approval | IECEx PTB 11.0034 |
Mass | approx. 150 g |
Control elements | DIP-switch |
Ripple | ≤ 10 % |
EU-type examination certificate | PTB 00 ATEX 2080 |
Certificate | V 99 ATEX 1493 X |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Degree of protection | IEC 60529:2001 |
Display elements | LEDs |
Safety Integrity Level (SIL) | SIL 2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Rated voltage | 20 ... 30 V DC |
Rated current | ≤ 30 mA |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Configuration | via DIP switches |
Buy Pepperl+Fuchs KFD2-SR2-Ex1.W with the best possible price and delivery terms on eltra-trade.com
Eltra Trade s.r.o. is fast developing company in automation instrumentation. Due to a wide range of brands, we allow you to refuse many other suppliers greatly saving your time. We provide delivery all over the world. We will help you to save money with our lowest prices. We are keeping you up-to-date with Tracking Numbers throughout the process. We always fulfill our obligations.