Pepperl+Fuchs KFD2-SRA-Ex4
Switch Amplifier

Pepperl+Fuchs KFD2-SRA-Ex4
  • 4-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • 50 % less wiring, 2:1 technology
  • Relay contact output
  • Line fault detection (LFD)
  • Reversible mode of operation
Item Number: KFD2-SRA-Ex4
430.00
-
+
Total price: 430.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments

Ripple10 %

Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Line fault detectionbreakage I 0.15 mA , short-circuit I > 6 mA
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
- terminal module F-KD-Ex2
- terminal module F-KDR-Ex2
Display elementsLEDs
Power dissipation1.2 W
Mechanical life5 x 106 switching cycles
Control elementsDIP-switch
InputEN 60947-5-6:2000
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Signal typeDigital Input
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Energized/De-energized delayapprox. 30 ms / approx. 30 ms
Connectionoutput I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12
Electromagnetic compatibilityNE 21:2006
Output/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Degree of protectionIEC 60529:2001
Rated current45 ... 70 mA
ConnectionPower Rail or terminals 14+, 15-
Connection sidecontrol side
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Degree of protectionIP20
Massapprox. 150 g
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I ... IVSignal I ... Signal IV ; relay
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Connection sidefield side
Switching frequency10 Hz (non-AC operation) 3 Hz (AC operation)
Contact loading253 V AC/2 A /cos andphi; > 0.7; 40 V DC/2 A resistive load;
Connectionscrew terminals
Configurationvia DIP switches
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Pulse/Pause ratiomin. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation)
Collective error messagePower Rail
IECEx approvalIECEx TUN 04.0003
Rated voltage19 ... 30 V DC
Labelingspace for labeling at the front
EU-Type Examination CertificateZELM 99 ATEX 0009
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Connectionterminals 1-, 2+, 3-; 4-, 5+, 6-

Comments

No comments yet

Write a comment