Pepperl+Fuchs KFD2-SRA-Ex4
Switch Amplifier
- 4-channel isolated barrier
- 24 V DC supply (Power Rail)
- Dry contact or NAMUR inputs
- 50 % less wiring, 2:1 technology
- Relay contact output
- Line fault detection (LFD)
- Reversible mode of operation
Item Number:
KFD2-SRA-Ex4
The price is not final. Please check with the manager!
Contact our experts
- Overview
- Comments
Ripple10 %
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data |
Line fault detection | breakage I 0.15 mA , short-circuit I > 6 mA |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) - terminal module F-KD-Ex2 - terminal module F-KDR-Ex2 |
Display elements | LEDs |
Power dissipation | 1.2 W |
Mechanical life | 5 x 106 switching cycles |
Control elements | DIP-switch |
Input | EN 60947-5-6:2000 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Signal type | Digital Input |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Energized/De-energized delay | approx. 30 ms / approx. 30 ms |
Connection | output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12 |
Electromagnetic compatibility | NE 21:2006 |
Output/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Degree of protection | IEC 60529:2001 |
Rated current | 45 ... 70 mA |
Connection | Power Rail or terminals 14+, 15- |
Connection side | control side |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Degree of protection | IP20 |
Mass | approx. 150 g |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output I ... IV | Signal I ... Signal IV ; relay |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Connection side | field side |
Switching frequency | 10 Hz (non-AC operation) 3 Hz (AC operation) |
Contact loading | 253 V AC/2 A /cos andphi; > 0.7; 40 V DC/2 A resistive load; |
Connection | screw terminals |
Configuration | via DIP switches |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Pulse/Pause ratio | min. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation) |
Collective error message | Power Rail |
IECEx approval | IECEx TUN 04.0003 |
Rated voltage | 19 ... 30 V DC |
Labeling | space for labeling at the front |
EU-Type Examination Certificate | ZELM 99 ATEX 0009 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Connection | terminals 1-, 2+, 3-; 4-, 5+, 6- |