Pepperl+Fuchs KFD2-ST2-Ex1.LB
Switch Amplifier

Pepperl+Fuchs KFD2-ST2-Ex1.LB
We ship to United States of America!
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Active transistor output
  • Active fault output
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Up to SIL 2 acc. to IEC 61508
Item Number: KFD2-ST2-Ex1.LB
Price on Request
-
+
Total price: 0.00
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
  • Overview +
  • Comments +
Connection sidecontrol side
Input/power supplyreinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms
ConnectionPower Rail or terminals 14+, 15-
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Labelingspace for labeling at the front
Rated current 50 mA
Ambient temperature-20 ... 60 ?°C (-4 ... 140 ?°F)
Connectionscrew terminals
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Ripple 10 %
Degree of protectionIEC 60529:2001
Switching frequency 5 kHz
Output/power supplynot available , common pole terminal 14+
Control elementsDIP-switch
Output IIsignal or error message , electronic output, active
Input/Outputreinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms
Safety Integrity Level (SIL)SIL 2
Signal level1-signal: (L+) - 3.5 V (100 mA, short-circuit protected)
0-signal: switched off (off-state current 10 andmicro;A)
Output/Outputnot available , common pole terminal 14+
Configurationvia DIP switches
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
InputEN 60947-5-6:2000
Output Isignal , electronic output, active
Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Display elementsLEDs
Connection sidefield side
CertificateT??V 99 ATEX 1499 X
Signal typeDigital Input
Collective error messagePower Rail
Massapprox. 150 g
Connectionoutput I: terminals 7+ ; output II: terminals 9+
Line fault detectionbreakage I 0.1 mA , short-circuit I > 6 mA
Rated voltage20 ... 30 V DC
EU-Type Examination CertificatePTB 00 ATEX 2035
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Degree of protectionIP20
Galvanic isolationIEC 62103:2003
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Connectionterminals 1+, 2+, 3-
Electromagnetic compatibilityNE 21:2004

Buy Pepperl+Fuchs KFD2-ST2-Ex1.LB with the best possible price and delivery terms on eltra-trade.com