Pepperl+Fuchs KFD2-ST2-Ex1.LB
Switch Amplifier
We ship to United States of America!
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Dry contact or NAMUR inputs
- Active transistor output
- Active fault output
- Line fault detection (LFD)
- Reversible mode of operation
- Up to SIL 2 acc. to IEC 61508
Item Number:
KFD2-ST2-Ex1.LB
Delivery standard: 3-6 weeks, depending on the country.
Condition: new
Contact our experts
- Overview +
- Comments +
Connection side | control side |
Input/power supply | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms |
Connection | Power Rail or terminals 14+, 15- |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Labeling | space for labeling at the front |
Rated current | 50 mA |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Connection | screw terminals |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Ripple | 10 % |
Degree of protection | IEC 60529:2001 |
Switching frequency | 5 kHz |
Output/power supply | not available , common pole terminal 14+ |
Control elements | DIP-switch |
Output II | signal or error message , electronic output, active |
Input/Output | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 Vrms |
Safety Integrity Level (SIL) | SIL 2 |
Signal level | 1-signal: (L+) - 3.5 V (100 mA, short-circuit protected) 0-signal: switched off (off-state current 10 andmicro;A) |
Output/Output | not available , common pole terminal 14+ |
Configuration | via DIP switches |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Input | EN 60947-5-6:2000 |
Output I | signal , electronic output, active |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Display elements | LEDs |
Connection side | field side |
Certificate | T??V 99 ATEX 1499 X |
Signal type | Digital Input |
Collective error message | Power Rail |
Mass | approx. 150 g |
Connection | output I: terminals 7+ ; output II: terminals 9+ |
Line fault detection | breakage I 0.1 mA , short-circuit I > 6 mA |
Rated voltage | 20 ... 30 V DC |
EU-Type Examination Certificate | PTB 00 ATEX 2035 |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
Degree of protection | IP20 |
Galvanic isolation | IEC 62103:2003 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Connection | terminals 1+, 2+, 3- |
Electromagnetic compatibility | NE 21:2004 |
Buy Pepperl+Fuchs KFD2-ST2-Ex1.LB with the best possible price and delivery terms on eltra-trade.com