Pepperl+Fuchs KFD2-STC4-Ex1
SMART Transmitter Power Supply

Pepperl+Fuchs KFD2-STC4-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
  • Output 0/4 mA ... 20 mA
  • Terminals with test points
  • Up to SIL 2 acc. to IEC 61508
Item Number: KFD2-STC4-Ex1
418.23
-
+
Total price: 418.23
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
KFD2-STC4-EX1 art 283672

Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

EU-Type Examination CertificateBAS 99 ATEX 7060 X
Connection sidefield side
Equipmentterminals 2-, 3
Connectionterminals 1+, 2-, 3 or 5-, 6+
Degree of protectionIEC 60529:2001
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Deviationat 20 В°C (68 В°F), 0/4 ... 20 mA
10 andmicro;A incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Voltage drop2.4 V at 20 mA (terminals 5, 6)
Degree of protectionIP20
Electromagnetic compatibilityNE 21:2011
Rise time/fall time20 micro/s
Protection against electrical shockUL 61010-1:2012
Signal typeAnalog input
Equipmentterminals 5-, 6+
Equipmentterminals 1+, 3-
Available voltage16 V at 20 mA terminals 1+, 3
Equipmentterminals 1+, 2 / 3-
Labelingspace for labeling at the front
Load0 ... 800 andOmega; at 20 mA
CertificateTГњV 99 ATEX 1499 X
Output signal0/4 ... 20 mA (overload > 25 mA)
Connectionterminals 7-, 8+, 9
Settling time200 micro/s
Connection sidecontrol side
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Power consumption1.8 W
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Safety Integrity Level (SIL)SIL 2
Display elementsLED
Ripplemax. 50 andmicro;A rms
Power dissipation1.4 W
Input resistance64 andOmega; terminals 2-, 3 ; 500 andOmega; terminals 1+, 3 (250 andOmega; load)
Connectionscrew terminals
Rated voltage20 ... 35 V DC
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2
Input signal0/4 ... 20 mA
Ripplewithin the supply tolerance
IECEx approvalIECEx BAS 04.0016X
IECEx CML 15.0055X
ConnectionPower Rail or terminals 14+, 15-
Massapprox. 200 g

Comments

No comments yet