Pepperl+Fuchs KFD2-STC4-Ex1.2O
SMART Transmitter Power Supply
1-channel isolated barrier
24 V DC supply (Power Rail)
- Overview +
- Comments +
Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
Signal splitter (1 input and 2 outputs)
Dual output 0/4 mA ... 20 mA
Terminal blocks with test sockets
Up to SIL 3 acc. to IEC 61508
Display elements | LED |
Note | Both output loads must be connected to ensure complete and correct operation within the technical specification. Open circuit of one of the two outputs will not affect the connected output, but would result in a loss of transmitter supply voltage of up to 0.7 Volt. |
Settling time | 200 µs |
Ripple | max. 50 µA rms |
IECEx approval | IECEx BAS 04.0016X IECEx CML 15.0055X |
Equipment | terminals 5-, 6+ |
Rise time/fall time | 20 µs |
Ambient temperature | -20 ... 60 ?°C (-4 ... 140 ?°F) |
Electromagnetic compatibility | NE 21:2011 |
Rated voltage | 20 ... 35 V DC |
Signal type | Analog input |
Power dissipation | 1.8 W |
Connection | Power Rail or terminals 14+, 15- |
Mass | approx. 200 g |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB) |
Voltage drop | terminals 5, 6 : ≤ 2.4 V at 20 mA |
Input signal | 0/4 ... 20 mA |
Degree of protection | IP20 |
Deviation | at 20 ?°C (68 ?°F), 0/4 ... 20 mA ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
Certificate | T??V 99 ATEX 1499 X |
Protection against electrical shock | UL 61010-1:2012 |
Ripple | within the supply tolerance |
Connection | terminals 1+, 2-, 3 or 5-, 6+ |
Open circuit voltage/short-circuit current | terminals 1+, 3-: 22.7 V / 38 mA |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 |
Output/Output | functional insulation, rated insulation voltage 50 V AC |
Power consumption | 2.4 W |
Equipment | terminals 1+, 3- |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
EU-type examination certificate | BAS 99 ATEX 7060 X |
Connection | terminals 7-, 8+,9; 10-, 11+,12 |
Connection | screw terminals |
Output signal | 0/4 ... 20 mA (overload > 25 mA) |
Connection side | field side |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Degree of protection | IEC 60529:2001 |
Safety Integrity Level (SIL) | SIL 3 |
Load | 0 ... 550 Ω at 20 mA |
Equipment | terminals 1+, 2 / 3- |
Connection side | control side |
Equipment | terminals 2-, 3 |
Labeling | space for labeling at the front |
Available voltage | terminals 1+, 3: ≥ 16 V at 20 mA |
Input resistance | terminals 2-, 3: max. 76 Ω terminals 1+, 3: max. 500 Ω (250 Ω load) |