Pepperl+Fuchs KFD2-STC4-Ex1.H
SMART Transmitter Power Supply

Pepperl+Fuchs KFD2-STC4-Ex1.H
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
  • Output 0/4 mA ... 20 mA
  • Terminals with test points
  • High field voltage 17.6 V DC
  • Up to SIL 2 acc. to IEC 61508
Item Number: KFD2-STC4-Ex1.H
415.02
-
+
Total price: 415.02
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Labelingspace for labeling at the front
Equipmentterminals 5-, 6+
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2
Input resistance≤ 64 Ω terminals 2-, 3 ; ≤ 500 Ω terminals 1+, 3 (250 Ω load)
Connection sidecontrol side
Electromagnetic compatibilityNE 21:2011
Power consumption1.9 W
Safety Integrity Level (SIL)SIL 2
Massapprox. 200 g
Available voltage≥ 17.6 V at 20 mA terminals 1+, 3
Equipmentterminals 1+, 3-
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
EU-type examination certificateBAS 99 ATEX 7060 X
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Output signal0/4 ... 20 mA (overload > 25 mA)
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Input signal0/4 ... 20 mA
Signal typeAnalog input
Rise time/fall time20 µs
Degree of protectionIP20
Ripplewithin the supply tolerance
CertificateTГњV 99 ATEX 1499 X
Power dissipation1.5 W
Protection against electrical shockUL 61010-1:2012
Connectionterminals 7-, 8+, 9
Connectionterminals 1+, 2-, 3 or 5-, 6+
Deviationat 20 В°C (68 В°F), 0/4 ... 20 mA
≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Ripplemax. 50 µA rms
Display elementsLED
Equipmentterminals 2-, 3
Settling time200 µs
ConnectionPower Rail or terminals 14+, 15-
Load0 ... 800 Ω at 20 mA
Connectionscrew terminals
Connection sidefield side
IECEx approvalIECEx BAS 04.0016X
IECEx CML 15.0055X
Equipmentterminals 1+, 2 / 3-
Rated voltage20 ... 35 V DC
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Degree of protectionIEC 60529:2001
Voltage drop≤ 2.4 V at 20 mA (terminals 5, 6)

Comments

No comments yet

Write a comment