2-channel signal conditioner
24 V DC supply (Power Rail)
- Overview
- Comments
Input/Outputbasic insulation according to IEC 61010-1, rated insulation voltage 300 Veff
Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
Output 0/4 mA ... 20 mA current sink/current source
Terminals with test points
Up to SIL 2 acc. to IEC 61508
Load | 0 ... 600 andOmega; |
Connection | Power Rail or terminals 14+, 15- |
Available voltage | 16 V at 20 mA, terminals 1+, 3 |
Output/Output | functional insulation, rated insulation voltage 50 V AC |
Connection | terminals 1+, 2-, 3; 4+, 5-, 6 |
Input signal | 0/4 ... 20 mA |
Input/power supply | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff |
Settling time | 200 micro/s |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 |
Power consumption | 2.6 W at maximum load |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Connection | terminals 7+, 8-, 9-; 10+, 11-, 12- (sink) terminals 7-, 8+, 9+; 10-, 11+, 12+ (source) see additional information |
Signal type | Analog input |
Electromagnetic compatibility | NE 21:2012 EN 61326-3-2:2008 |
Safety Integrity Level (SIL) | SIL 2 |
Connection side | control side |
Connection side | field side |
Output signal | 0/4 ... 20 mA (overload > 25 mA) |
Ripple | max. 50 andmicro;A rms |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Mass | approx. 150 g |
Rated voltage | 18 ... 30 V DC |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Protection against electrical shock | UL 61010-1:2012 |
Ripple | within the supply tolerance |
Power dissipation | 1.4 W at maximum load |
Display elements | LED |
Rise time/fall time | 100 micro/s |
Degree of protection | IEC 60529:2001 |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) |
Labeling | space for labeling at the front |
Connection | screw terminals |
Deviation | at 20 В°C (68 В°F), 0/4 ... 20 mA 10 andmicro;A incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
External supply (loop) | 2 ... 30 V DC |
Degree of protection | IP20 |
Ambient temperature | -20 ... 60 В°C (-4 ... 140 В°F) |
Input resistance | max. 265 andOmega; terminals 2-, 3; 5-, 6 , max. 330 andOmega; terminals 1+, 3; 4+, 6 |
Frequency range | field side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB) safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB) |
Comments