Pepperl+Fuchs KFD2-STC5-Ex1.H
SMART Transmitter Power Supply

Pepperl+Fuchs KFD2-STC5-Ex1.H
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
  • Output 0/4 mA ... 20 mA current sink/current source
  • Terminals with test points
  • High field voltage 17 V DC
  • Up to SIL 2 acc. to IEC 61508
Item Number: KFD2-STC5-Ex1.H
363.23
-
+
Total price: 363.23
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
Equipmentterminals 2-, 3
Connectionscrew terminals
Rise time/fall time100 micro/s
Settling time200 micro/s
Available voltage 17 V at 20 mA , terminals 1+, 3-
Input resistancemax. 265 andOmega; terminals 2-, 3 , max. 330 andOmega; terminals 1+, 3
Load0 ... 800 andOmega;
IECEx approvalIECEx CML 17.0015X
Dimensions20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2
ConnectionPower Rail or terminals 14+, 15-
Degree of protectionIEC 60529:2001
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Protection against electrical shockUL 61010-1:2012
CertificateCML 17 ATEX 3028X
Degree of protectionIP20
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)
Connection sidefield side
Power dissipation 1 W at maximum load
Deviationat 20 В°C (68 В°F), 0/4 ... 20 mA
10 andmicro;A incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Labelingspace for labeling at the front
Equipmentterminals 1+, 2 / 3-
EU-Type Examination CertificateCML 17 ATEX 2029X
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
Rated voltage18 ... 30 V DC
Massapprox. 200 g
Equipmentterminals 1+, 3-
Safety Integrity Level (SIL)SIL 2
External supply (loop)2 ... 30 V DC
Input signal0/4 ... 20 mA
Display elementsLED
Output signal0/4 ... 20 mA (overload > 25 mA)
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Connection sidecontrol side
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Signal typeAnalog input
Ripplemax. 50 andmicro;A rms
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Power consumption 1.6 W at maximum load
Ripplewithin the supply tolerance
Connectionterminals 1+, 2-, 3
Connectionterminals 7+, 8-, 9- (sink)
terminals 7-, 8+, 9+ (source)
see additional information