Pepperl+Fuchs KFD2-UFC-Ex1.D
Frequency Converter with Trip Values

Pepperl+Fuchs KFD2-UFC-Ex1.D
  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

  • Input for NAMUR sensors or dry contacts

Item Number: KFD2-UFC-Ex1.D
690.00
-
+
Total price: 690.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
  • Configurationvia operating buttons

  • via PACTware

  • Input frequency 1 mHz ... 5 kHz

  • Current output 0/4 mA ... 20 mA

  • Relay contact and transistor output

  • Start-up override

  • Line fault detection (LFD)

  • Up to SIL 2 acc. to IEC 61508/IEC 61511

Input I

terminals 1+, 3-: Ex ia

Connection

Input I: intrinsically safe: terminals 1+, 3-

Input II: non-intrinsically safe: terminals 13+, 14-

Input II

terminals 13+, 14- non-intrinsically safe

Rated current

approx. 100 mA

Output I, II

signal, relay

Output III/IV

basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff

Connection

output I: terminals 10, 11, 12

output II: terminals 16, 17, 18

outout III: terminasl 19+, 20-

output IV: terminals 8+, 7-

Safety Integrity Level (SIL)

SIL 2

Start-up override/power supply and collective error

functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff

Collective error message

Power Rail

Output IV/power supply and collective error

functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff

Degree of protection

IP20

Power dissipation/power consumption

2 W / 2.2 W

Input

EN 60947-5-6:2000

EU-Type Examination Certificate

TГњV 99 ATEX 1471

Degree of protection

IEC 60529:2001

Connection

terminals 23+, 24- or power feed module/Power Rail

Mass

300 g

Certificate

TГњV 02 ATEX 1885 X

Output IV

terminals 8+, 7- non-intrinsically safe

Interface

RS 232

Display elements

LEDs , display

Programming interface

programming socket

Input I

sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact

Mounting

on 35 mm DIN mounting rail acc. to EN 60715:2001

Electromagnetic compatibility

NE 21:2006

Output I, II

terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe

Mutual output I, II, III

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

IECEx approval

IECEx TUN 04.0007

Input II

startup override: 1 ... 1000 s, adjustable in steps of 1 s

Interface/power supply and collective error

functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff

Output I, II/other circuits

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output III/power supply and collective error

basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff

Output IV

analog

Signal type

Digital Input

Connection

screw terminals

Ambient temperature

-20 ... 60 В°C (-4 ... 140 В°F)

Dimensions

40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3

Input I/other circuits

reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Connection side

control side

Connection side

field side

UL approval

E223772

Control elements

Control panel

Output III

electronic output, passive

Rated voltage

20 ... 30 V DC

Interface/output III

basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff

Labeling

space for labeling at the front

Supplementary information

Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Output III/start-up override

basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff

Output III

terminals 19+, 20- non-intrinsically safe

Comments

No comments yet

Write a comment