Pepperl+Fuchs KFD2-UT2-1
Universal Temperature Converter

Pepperl+Fuchs KFD2-UT2-1
  • 1-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Thermocouple, RTD, potentiometer or voltage input
  • Current output 0/4 mA ... 20 mA
  • Sink or source mode
  • Configurable by PACTware
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL 2 acc. to IEC 61508/IEC 61511
Item Number: KFD2-UT2-1
283.00
-
+
Total price: 283.00
The price is not final. Please check with the manager!
Contact our experts
  • Overview
  • Comments
KFD2-UT2-1 art.248759
Ripple within the supply tolerance
Connectionterminals 1, 2, 3, 4
Configurationvia PACTware
OutputAnalog current output
Programming interfaceprogramming socket
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
Electromagnetic compatibilityNE 21:2006
Input resistance1 MandOmega; (-100 ... 100 mV)
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Connectionoutput I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-)
Connection sidecontrol side
Rated voltage20 ... 30 V DC
Labelingspace for labeling at the front
Connectionterminals 14+, 15- or power feed module/Power Rail
Potentiometer0 ... 20 kandOmega; (2-wire connection), 0.8 ... 20 kandOmega; (3-wire connection)
Ambient temperature-20 ... 60 В°C (-4 ... 140 В°F)
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Connection sidefield side
Power dissipation/power consumption0.98 W / 0.98 W
Degree of protectionIEC 60529:2001
Connectionscrew terminals
Signal typeAnalog input
Safety Integrity Level (SIL)SIL 2
Massapprox. 130 g
Display elementsLEDs
Voltageselectable within the range -100 ... 100 mV
Degree of protectionIP20

Comments

No comments yet

Write a comment